TMT182
7 Maintenance
Hauser
29
Type of input
10.3
Output
Output signal
Analog 4 to 20 mA, 20 to 4 mA
Breakdown information
Breakdown information to NAMUR NE 43
Breakdown information is created when the measuring information is invalid or not present any-
more and gives a complete listing of all errors occuring in the measuring system.
Input
Designation
Measuring range limits
Min. span
Resistance thermometer (RTD)
to IEC 751
(
α
= 0.00385)
to JIS C1604-81
(
α
= 0.003916)
to DIN 43760
(
α
= 0.006180)
Pt100
Pt500
Pt1000
Pt100
Ni100
Ni500
Ni1000
-328 to 1562 °F (-200 to 850 °C)
-328 to 482 °F (-200 to 250 °C)
-328 to 482 °F (-200 to 250 °C)
-328 to 1200 °F (-200 to 649 °C)
-76 to 482 °F (-60 to 250 °C)
-76 to 302 °F (-60 to 150 °C)
-76 to 302 °F (-60 to 150 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
18 °F (10 °C)
• Connection type: 2-, 3- or 4-wire connection
• Software compensation of cable resistance possible in the 2 wire system (0 to 30
Ω
)
• Sensor cable resistance max. 20
Ω
per cable in the 3 and 4 wire system
• Sensor current:
≤
0.2 mA
• Corrosion detection as per NAMUR NE 89 for Pt100 4-wire connection (optional for 'Advanced Diagnostics' version,
see 'Product structure'). If corrosion detection is active, the response time is 2 s
Resistance transmitter
Resistance
Ω
10 to 400
Ω
10 to 2000
Ω
10
Ω
100
Ω
Thermocouples (TC)
to NIST Monograph 175,
IEC 584
to ASTM E988
to DIN 43710
Type B (PtRh30-PtRh6)
a
Type E (NiCr-CuNi)
Type J (Fe-CuNi)
Type K (NiCr-Ni)
Type N (NiCrSi-NiSi)
Type R (PtRh13-Pt)
Type S (PtRh10-Pt)
Type T (Cu-CuNi)
Type C (W5Re-W26Re)
Type D (W3Re-W25Re)
Type L (Fe-CuNi)
Type U (Cu-CuNi)
32 to 3308 °F
(0 to +1820 °C)
-454 to 1832 °F (-270 to +1000 °C)
-346 to 2192 °F (-210 to +1200 °C)
-454 to 2501 °F (-270 to +1372 °C)
-454 to 2372 °F (-270 to +1300 °C)
-58 to 3214 °F (-50 to +1768 °C)
-58 to 3214 °F (-50 to +1768 °C)
-454 to 752 °F (-270 to +400 °C)
32 to 4208 °F (0 to +2320 °C)
32 to 4523 °F (0 to +2495 °C)
-328 to 1652 °F (-200 to +900 °C)
-328 to 1112 °F (-200 to +600 °C)
900 °F (500 °C)
90 °F (50 °C)
90 °F (50 °C)
90 °F (50 °C)
90 °F (50 °C)
900 °F (500 °C)
900 °F (500 °C)
90 °F (50 °C)
900 °F (500 °C)
900 °F (500 °C)
90 °F (50 °C)
90 °F (50 °C)
• Internal cold junction (Pt100)
• Accuracy of cold junction: ± 1.8 °F (1 °C)
Voltage transmitter (mV)
Millivolt transmitter (mV)
-10 to 75 mV
5 mV
a.High measuring error increase for temperature lower than 572 °F (300 °C)
Signal (mA)
Under ranging
Standard
3.8
Over ranging
Standard
20.5
Sensor break; sensor short circuit low
To NAMUR NE 43
≤
3.6
Sensor break; sensor short circuit high
To NAMUR NE 43
≥
21.0