7 Maintenance
TMT182
26
Hauser
9.3
Application faults without messages
Application fault without
messages
General application faults
Application faults for RTD connection (Pt100/Pt500/Pt1000/Ni100)
106
Up-/Download active
None (will be automatically
acknowledged)
201
Warning: Measured value too small
Enter other values for measured
value range start
202
Warning: Measured value too large
Enter other values for measured
value range end
203
Unit is reset (to factory default
settings)
None
Fault code
Cause
Action/cure
Fault
Cause
Action/cure
No communication
No power supply on 2 wire circuit
Check current loop
Power supply too low (<10 V)
Connect cables correctly to terminal
plan (polarity)
Defective interface cable
Check interface cable
Defective interface
Check PC interface
Defective head transmitter
Replace head transmitter
Fault
Cause
Action/cure
Fault current
(
≤
3.6 mA or
≥
21 mA)
Defective sensor
Check sensor
Incorrect RTD connection
Reconnect cables correctly (connec-
tion diagram)
Incorrect 2 wire connection
Connect cables correctly to terminal
plan (polarity)
Transmitter programming faulty (wire
number)
Change parameter ’CONNECTION’
(See “Description of unit functions”
on page 20.)
Programming
Thermocouple set up (see
chapter 6.2.5); change to RTD
Defective head transmitter
Replace head transmitter
Measured value incorrect/inaccurate
Faulty sensor installation
Install sensor correctly
Heat conducted via sensor
Take note of sensor installation
length
Transmitter programming faulty (wire
number)
Change parameter ‘Connection type’
Transmitter programming faulty (scale)
Change scale
Wrong RTD used
Change parameter ‘Sensor type’
Sensor connection (2 wire)
Check sensor connections
Sensor cable (2 wire) not compensated
Compensate cable resistance
Offset incorrectly set
Check offset