6 Commissioning
Hauser
21
Function group: BASIC CALIBRATION
Type of sensor
• V2H0
Entry of sensor used:
Sensor type Range start Range end value
-10..75 mV
-10 mV
75 mV
10..400 Ohm
10
Ω
400
Ω
10..2000 Ohm
10
Ω
2000
Ω
Pt100 DIN
-200 °C (-328 °F)
850 °C (1562 °F)
Pt100 JIS
-200 °C (-328 °F)
649 °C (482 °F)
Pt500
-200 °C (-328 °F)
250 °C (482 °F)
Pt1000
-200 °C (-328 °F)
250 °C (482 °F)
Ni100
-60 °C (-76 °F)
180 °C (356 °F)
Ni500
-60 °C (-76 °F
150 °C (302 °F)
Ni1000
-60 °C (-76 °F
150 °C (302 °F)
Polynom RTD
-270 °C (-454 °F)
2500 °C (4532 °F)
Type B
0 °C (32 °F)
1820 °C (3308 °F)
Type C
0 °C (32 °F)
2320 °C (4208 °F)
Type D
0 °C (32 °F)
2495 °C (4523 °F)
Type E
-270 °C (-454 °F)
1000 °C (1832 °F)
Type J
-210 °C (-346 °F)
1200 °C (2192 °F)
Type K
-270 °C (-454 °F)
1372 °C (2501 °F)
Type L
-200 °C (-328 °F)
900 °C (1652 °F)
Type N
-270 °C (-454 °F)
1300 °C (2372 °F)
Type R
-50 °C (-58 °F)
1768 °C (3214 °F)
Type S
-50 °C (-58 °F)
1768 °C (3214 °F)
Type T
-270 °C (-454 °F)
400 °C (752 °F)
Type U
-200 °C (-328 °F)
600 °C (1112 °F)
Polynom TC
-270 °C (-454 °F)
2500 °C (4532 °F)
Pt100 DIN
Temp.Compensation
• V2H1
Selection of temperature compensation of the cold junction when using customer
specific linearization of the TC polynom
Input:
None, Type B, Type C, Type D, Type E, Type J, Type K, Type L, Type N, Type R,
Type S, Type T, Type U
None
Unit meas. value
• V2H2
Enter engineering units.
Entry: °C
°F
K
°C
Current output
• V2H3
Enter standard (4 to 20 mA) or inverse (20 to 4 mA) current output signal.
Entry: 4 to 20 mA
20 to 4 mA
4 to 20 mA
Value for 4 mA
• V2H4
Entry: For limits see unit function SENSOR TYPE.
0 °C
Value for 20 mA
• V2H5
Entry: For limits see unit function SENSOR TYPE.
100 °C
Connection
• V2H6
•
7
RTD connection
Entry of RTD connection mode
Entry: 2
wire
3 wire
4 wire
3 wire
!
Note!
Function field is only active on selection of resistance thermometer (RTD) in the unit
function SENSOR TYPE (V2H0)