Proline Promag P 500 HART
Commissioning
Hauser
117
Parameter
Description
Selection / User interface /
User entry
Factory setting
Assign pulse output 1
Select process variable for pulse output.
• Off
• Volume flow
• Mass flow
• Corrected volume flow
Off
Measuring mode
Select measuring mode for pulse output.
• Forward flow
• Forward/Reverse flow
• Reverse flow
• Reverse flow compensation
Forward flow
Value per pulse
Enter measured value at which a pulse is
output.
Signed floating-point number
Depends on country and
nominal diameter
Pulse width
Define time width of the output pulse.
0.5 to 2
000 ms
0.5 ms
Failure mode
Define output behavior in alarm condition.
• Actual value
• No pulses
No pulses
Invert output signal
Invert the output signal.
• No
• Yes
No