Cerabar PMP51B Analog
Diagnostics and troubleshooting
Hauser
35
9
Diagnostics and troubleshooting
9.1
General troubleshooting
9.1.1
General errors
Device not responding
• Possible cause: Supply voltage does not match the specification on the nameplate
Remedial action: Apply the correct voltage
• Possible cause: The polarity of the supply voltage is wrong
Remedial action: Correct the polarity
• Possible cause: The cables do not contact the terminals properly
Remedial action: Check the electrical contact between cables and correct if necessary
• Possible cause: Load resistance too high
Remedial action: Increase the supply voltage to reach the minimum terminal voltage
No values visible on the display
• Possible cause: The plug of the display cable is not connected correctly
Remedial action: Connect the plug correctly
• Possible cause: Display is defective
Remedial action: Replace the display
9.1.2
Measures
Take the following measures if an error message is displayed:
• Check the cable/power supply
• Check the plausibility of the pressure value
• Restart the device
• Perform a reset (the device may need to be reconfigured)
If the measures do not rectify the problem, contact your Hauser office.