93
Professional mode
Under ›Recooling‹, determine whether
cooling is to be effected down to
›T min tank‹ or ›T max tank‹.
Under ›n pump‹ set the
pump speed in percent.
Enter the hysteresis value by ›Hyst‹.
If necessary, activate ›Soft charging‹
›dT‹ is used to define the switch-ON
temperature for the holiday function
as a difference from the preset
maximum temperature of the tank.
Continue to scroll.
To avoid overheating of the plant,
the controller will suppress yield
optimization while the holiday
function is activated.
The time frame of the holiday function
is mostly defined in operation mode.
If tank cooling is activated, an
appropriate time frame must be
defined - this makes sense during the
cooler hours of the night - by allowing
the controller to dissipate as much
energy as possible via the collectors.
Continue to scroll.
Start of holiday
End of holiday
Tank cooling
Start
End
19.07.2013
02.08.2013
00:00
07:00
1.3.3 Holiday function
25.08.2012
10:35
Re-cooling
n pump
Hyst.
Soft charge
dT
T-min tank
100%
5.0K
5.0K
1.3.3 Holiday function
25.08.2012
10:35