9
Technical Data
Interfaces TS1 - TS8
Design
2 spring-type terminals each
Assignment as inputs
Admissible temperature probe
Temperature sensor Pt 1000
Optional assignment of
TS6-TS8 to the impeller sensor
DFZ 1-100 pulses/litre
Optional assignment as
PWM signal 100Hz...2kHz or
output on TS7/TS8
analogue output 0...10V, max. 10mA
Interfaces TS9 - TS10
Design
2 spring-type terminals each
Assignment to the impeller sensor
DFZ 1-100 pulses/litre
Assignment as output
PWM signal 100Hz...2kHz or
analogue output 0...10V, max. 10mA
Active outputs RO1-RO4 :Triac outputs
Design
3 spring-type terminals each, PE, N and L
Output voltage [VAC]
85-265
Output power max. per output [VA]
200
Output current max. per output [A]
1
Switching output REL: Floating change-over contact
Design
3 spring-type terminals
Switching voltage max. [V]
253
Switching capacity max. [VA]
230
Switching current max. [A]
1
Interface for analogue Vortex flow sensors
Design
1 multi-pin connector
5V/24V supply terminals
Design
1 spring-type terminal each
Output voltage [VDC]
5V/24V
Max. current per output [mA]
15
Supply terminals L
Design
1 spring-type terminal each
Output voltage [VAC]
85-265
The total current of all outputs including RO1-RO4 must not exceed 4A!