Professional mode
If the temperature in tank 1 exceeds
the value T limit 1, or if the temper-
ature in tank 2 exceeds the value
T limit 2, the solar circuit pump is
switched off unconditionally.
The pump is not switched on again
until the actual temperature falls be-
low the value T limit by the hysteresis
›Hyst‹.
Example: T limit =60°C minus Hys-
t=5K => Reclosing temperature 55°C.
Continue via the menu
item ›Max.temp.shutoff‹.
Maximum temperature of the tanks 1
and 2, to avoid excessively hot water
in the tank; the tank in question is
only charged to its ›T max‹.
In case of collector overheating, the
tank can be charged up to ›T-limit‹.
Continue via the menu item
›Min. temperature‹.
To increase efficiency on charging
the tanks, the minimum temperature
to be present at the collector in
question is entered via ›T min. Coll‹.
The relevant hysteresis value
represents the difference
between the switch-ON
and switch-OFF temperature.
Continue via the
menu item ›Priority charge‹.
Hysteresis
T limit 1
T limit 2
If T-limit>60°, anti-scalding
protection must be installed.
5.0K
60.0°C
60.0°C
1.2.3 Temp.limitation
25.08.2012
10:34
T max.tank 1
T max.tank 2
59.0°C
59.0°C
1.2.5 Max.temp.shutoff
25.08.2012
10:34
Activation
T min.Collector 1
Hyst. Collector 1
20.0°C
2.0K
1.2.6 Min. temperature
25.08.2012
10:34