Cassette Air Handler
TROUBLESHOOTINg pROCEdURE
for Cassette Air Handlers
All service should be performed by a
qualified service technician. Before
removing access panels or control
covers to expose moving parts or non-
insulated live electrical components,
disconnect all high volt power supplies
to both the indoor unit and outdoor unit.
Failure to do so could result in physical
injury and/or electrical shock.
When troubleshooting the indoor unit, refer
to the wiring diagram that is supplied with
the equipment. It is located on the back
of the control access panel. If unable to
locate the wiring diagram call the factory
technical service line at (800) 228-9364
and one can be faxed or mailed. Please
have the full model and serial number
available prior to calling.
!
!
WARNING
WALL THERMOSTAT CONTROL INTERCONNECT DIAgRAM
MODELS CAHA12, CAHA24, AND CACA36
EMI America Series air handlers are de
-
signed to operate with EMI America Se
-
ries condensers. The air handler (indoor
unit) and condenser (outdoor unit) are to
be independently connected to the electri
-
cal service panel and protected by sepa
-
rate time delay fuse or HACR breakers.
(See the unit name plate for the correct
breaker type and size). The indoor and
outdoor units are also connected to each
other via a 24 Vac, 18 AWG interconnect
wiring. A transformer provides the low volt
power source for the controls. The number
of low
Volt interconnect conductors will be
dependent on the control, heating options
and thermostat selected. Interconnect wire
should be at least 18 AWG. Refer to the
unit wiring diagram for the interconnect
diagram that matches your system
Figure #12