SEqUENCE Of OpERATION
PRoGRAmmING ScheDule
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Time Temp Time Temp Time Temp Time Temp Time Temp Time Temp Time Temp
Morning
Cool
Heat
:
:
:
:
:
:
:
Auto
Day
Cool
Heat
:
:
:
:
:
:
:
Auto
Evening
Cool
Heat
:
:
:
:
:
:
:
Auto
Night
Cool
Heat
:
:
:
:
:
:
:
Auto
To copy the settings from any day to the entire week:
1) Select the day to be copied.
2) Simultaneously press the "FAN" and "PROG" buttons for three seconds.
CONDENSATE FAULT 2 BLINKS:
If the control senses a condensate fault
condition either through the condensate
pumps safety switch or the drain pan sen
-
sors, the Timer/Alarm LED will flash two
(2) times to signify that a fault has oc
-
curred. The compressor will switch off for
a minimum of three (3) minutes AND until
the fault condition is corrected. After that,
so long as the thermostat is calling for
cooling the compressor will re-start.
ID COIL SENSOR FAULT 3 BLINKS:
The indoor coil sensor monitors the tem
-
perature of the indoor coil. If a freeze con
-
dition is detected continuously for three (3)
minutes, the Timer/Alarm LED will flash
three (3) times to signify that a fault has
occurred. The compressor will switch off
for a minimum of three (3) minutes AND
until the fault condition is corrected. Also,
if the microprocessor detects an evapora
-
tor freeze condition four (4) times within
a 24 hour period, the clean filter indicator
will appear.
CLEAN FILTER WARNINg 4 BLINKS:
To aid in filter maintenance, the Cassette
controller will indicate when a schedule
filter cleaning is required by flashing the
Timer/Alarm LED. During normal opera
-
tion the microprocessor will keep track of
the unit’s run time. When the clean filter
time has elapsed, the Timer/Alarm LED
will flash four (4) times to indicate that the
filter needs to be cleaned. The clean filter
time is selectable through the
Configura
-
tion Mode
of the
optional
Infrared Hand
Held Controller. Available settings are
250, 500, 750, 1000, and 1250 hours. For
Remote Thermostat Mode
the default time
is 1000 hrs. This cannot be changed. If
an evaporator freeze condition is detected
four (4) times within a 24 hour period, the
Clean Filter Alarm will appear.
After filter maintenance has been per
-
formed, press the “Clear Filter Warning
Button” for three (3) seconds. The control
will respond with a beep to indicate that
the timer has been reset.