www.enviromaster.com
47
Cassette Air Handler
CASSETTE ELECTRICAL SpECIfICATIONS
model #
fan motor
Elect Heat
Total
AmpS
min
Volt
m.C.A.
HACR
BRkR
Volts/Hz/pH
RLA
H.p.
kW
AmpS
CAH_12
208/230/60/1
0.35
1/10
–
–
0.4
197
0.5
15
CAH_12
208/230/60/1
0.35
1/10
1.5
6.52
6.9
197
8.6
15
CAH_24
208/230/60/1
0.55
1/8
–
–
0.6
197
0.7
15
CAH_24
208/230/60/1
0.55
1/8
3
13.04
13.6
197
17.0
20
CAC_36
208/230/60/1 0.5, 0.5
1/10, 1/10
–
–
1.0
197
1.2
15
CAC_36
208/230/60/1 0.5, 0.5
1/10, 1/10
5
21.74
22.7
197
28.3
30
CASSETTE SySTEm mATCHES
S1CA/S1HA
Side Discharge
Cassette
CASSETTE ELECTRICAL SpECIfICATIONS
NOTE:
Due to EMI’s ongoing product development program, all designs and specifications
are subject to change without notice.
SySTEmS WITH HEAT pUmp CASSETTE UNITS
Cassette
Condenser
Cooling Btuh Heating Btuh SEER
HSpf
SHR
EER
COp
Ref.
CAH_12
S1HA9000
9,000
8,000
13.0
7.7
0.80
11.6
3.3
R22
CAH_12
S1HA2000
11,800
10,800
13.0
7.7
0.72
11.4
3.4
R22
CAH_24
S1HA8000
18,000
15,000
13.0
7.7
0.78
12.0
3.3
R22
CAH_24
S1HA4000
23,000
20,000
13.0
7.7
0.69
11.7
3.3
R22
NOTE:
CAH_ refers to CAHA or CAHB
CAC_ refers to CACA or CACB
COOLINg SySTEmS WITH CASSETTE UNITS
Cassette
Condenser
Btuh
SEER
SHR
EER
Ref.
CAH_12
S1CA9000
9,000
13.0
0.79
11.7
R22
CAH_12
S1CA2000
11,800
13.0
0.72
12.2
R22
CAH_24
S1CA8000
18,000
13.0
0.76
12.3
R22
CAH_24
S1CA4000
23,000
13.0
0.67
11.8
R22
CAC_36
S1CA3000
30,000
14.0
0.82
12.0
R22
CAC_36
S1CA6000
36,000
13.0
0.74
12.0
R22
*
* Important - This system has been designed and
manufactured to meet EnERgy STAR criteria for
energy efficiency. However, proper refrigerant charge
and proper air flow are critical to achieve rated capac
-
ity and efficiency. Installation of this product should
follow the manufacturer’s refrigerant
charging and air flow instructions.
Fail-
ure to confirm proper charge and
airflow may reduce energy efficiency
and shorten equipment life.
Содержание CAC_36
Страница 2: ......
Страница 52: ...5780 Success Drive Rome NY 13440 Enviromaster International LLC www enviromaster com...