www.enviromaster.com
Cassette Air Handler
50
CASSETTE SySTEm mATCHES
SySTEm OpTIONS WITH T4CA TOp dISCHARgE
Cassette
Qty
Condenser
Btuh
SEER
SHR
EER
Ref.
CAH_12
4
T4CA9999
35,200
13.0
0.87
11.4
R22
CAH_12
4
T4CA2222
46,000
13.0
0.76
11.4
R22
CAH_12
4
T4CA9222
43,000
13.0
0.77
11.4
R22
CAH_12
4
T4CA9992
37,800
13.0
0.79
11.4
R22
CAH_12
4
T4CA9922
40,500
13.0
0.82
11.4
R22
SySTEm OpTIONS WITH T3HA TOp dISCHARgE
Cassette
qty
Condenser
Cooling
Btuh
Heating
Btuh
SEER
SHR
EER
COp
Ref
CAH_12
3
T3HA9920
29,800
25,800
13.0
0.78
11.7
3.1
R22
CAH_24
2+1
T3HA9980
36,400
29,000
13.0
0.77
12.2
3.1
R22
CAH_24
2+1
T3HA9940
42,500
35,800
13.0
0.72
11.9
3.1
R22
CAH_12
3
T3HA9220
31,800
27,800
13.0
0.76
11.6
3.1
R22
CAH_24
2+1
T3HA9280
38,500
31,000
13.0
0.75
12.1
3.1
R22
CAH_24
2+1
T3HA9240
44,500
37,800
13.0
0.71
11.8
3.1
R22
CAH_24
2+1
T3HA2280
40,500
33,200
13.0
0.75
12.0
3.1
R22
CAH_24
2+1
T3HA2240
46,500
40,000
13.0
0.71
11.8
3.1
R22
CAH-12
3
T3HA2220
34,000
30,000
13.0
0.75
11.6
3.1
R22
SySTEm OpTIONS WITH T4HA TOp dISCHARgE
Cassette
qty
Condenser
Cooling
Btuh
Heating
Btuh
SEER
SHR
EER
COp
Ref
CAH_12
4
T4HA9999
37,200
31,800
13.0
0.80
11.9
3.2
R22
CAH_12
4
T4HA9992
39,000
33,800
13.0
0.78
11.8
3.1
R22
CAH_12
4
T4HA9922
41,000
35,800
13.0
0.77
11.7
3.1
R22
CAH_12
4
T4HA9222
43,000
37,800
13.0
0.75
11.5
3.1
R22
CAH_12
4
T4HA2222
45,000
40,000
13.0
0.75
11.6
3.1
R22
NOTE:
CAH_ refers to CAHA or CAHB
CAC_ refers to CACA or CACB