www.enviromaster.com
17
Cassette Air Handler
S2CA /S2HA REfRIgERANT CHARgE TABLE
Condenser
Air handlers pairing
Line Chg/ft
factory Charge
Ref.
S2CA/S2HA9900
(2) CAH_12
.25 oz./ft (23g/m)
28 oz (794g)
R-22
S2CA/S2HA2200
(2) CAH_12
.25 oz./ft (23g/m)
33 oz (936g)
R-22
S2CA/S2HA9200
(2) CAH_12
.25 oz./ft (23g/m)
28 oz./ 33 oz. (794/936g)
R-22
S1CA/S1HA REfRIgERANT CHARgE TABLE
Condenser
Air handlers pairing
Line Chg/ft
factory Charge
Ref.
S1CA/S1HA9000
CAH_12
.25 oz./ft (23g/m)
37 oz. (1048g)
R-22
S1CA/S1HA2000
CAH_12
.25 oz./ft (23g/m)
40 oz. (1134g)
R-22
S1CA/S1HA8000
CAH_24
.56 oz./ft (52g/m)
51 oz. (1446g)
R-22
S1CA/S1HA4000
CAH_24
.56 oz./ft (52g/m)
65 oz. (1842g)
R-22
S1CA3000
CAC_36
.56 oz./ft (52g/m)
72 oz. (2041g)
R-22
S1CA6000
CAC_36
.56 oz./ft (52g/m)
90 oz. (2551g)
R-22
8. Charge to proper weight, charge
based on the length of interconnect
(see below).
NOTE:
Charging should be done with a
dial-a-charge or weighed in with a scale.
NOTE:
CAH_ refers to CAHA or CAHB
CAC_ refers to CACA or CACB
TOp dISCHARgE REfRIgERANT CHARgE CHART
Circuit Capacity
Line Chg/ft
A/C factory Charge
H/p factory Charge
Ref.
9,000
.25 oz./ft (23g/m)
28 oz. (794g)
42 oz. (1190g)
R-22
12,000
.25 oz./ft (23g/m)
30 oz. (850g)
46 oz. (1304g)
R-22
18,000
.56 oz./ft (52g/m)
48 oz. (1360g)
63 oz. (1786g)
R-22
24,000
.56 oz./ft (52g/m)
60 oz. (1701g)
80 oz. (2268g)
R-22
IMpORTANT NOTES:
I. To find the charge adjustment and system charge
for any air handlers and tubing length:
Line Adjustment = (Line Chg/Ft) x Line Length
System Total = Factory Line Adjustment
2. Round to the nearest ounce and allow for gaug-
es and hoses.
3. Use R22 refrigerant.
REfRIgERANT pROCESSINg
Refrigerant
Refer to Refrigerant
Charge Table for
specified line charge.
Содержание CAC_36
Страница 2: ......
Страница 52: ...5780 Success Drive Rome NY 13440 Enviromaster International LLC www enviromaster com...