EM12 User’s Manual
Appendix II
131
Code
Parameter Name
Setting range
Default
Property
b0-15 Frequency upper limit
Frequency lower limit (b0-17) ~ maximum frequency
(b0-13)
50.00 Hz
☆
b0-16
Frequency upper limit
offset
0.00 Hz~ maximum frequency(b0-13)
0.00 Hz
☆
b0-17 Frequency lower limit
0.00 Hz ~frequency upper limit(b0-15)
0.00 Hz
☆
b0-18 Rotation direction
0: Forward direction
1: Reverse direction
0
☆
b0-19
Base frequency for UP/
DOWN modification
during running
0: Running frequency
1: Setting frequency
0
★
b0-20
Acceleration/Deceleration
mode
0: Linear acceleration/ deceleration
1: S-curve acceleration/deceleration A
2: S-curve acceleration/deceleration B
0
☆
b0-21 Acceleration time 1
0.00s~650.00s (b0-25 = 2)
0.0s~6500.0s (b0-25 = 1)
0s~65000s (b0-25 = 0)
Model
dependent
☆
b0-22 Deceleration time 1
0.00s~650.00s (b0-25 = 2)
0.0s~6500.0s (b0-25 = 1)
0s~65000s (b0-25 = 0)
Model
dependent
☆
b0-23
Time proportion of
S-curve start segment
0.0% ~ (100.0% minus b0-24)
30.0%
☆
b0-24
Time proportion of
S-curve end segment
0.0% ~ (100.0% minus b0-23)
30.0%
☆
b0-25
Acceleration/Deceleration
time unit
0:1s
1: 0.1s
2: 0.01s
1
☆
b0-26
Acceleration/Deceleration
time base frequency
0: Maximum frequency (b0-13)
1: Set frequency
2: 100 Hz
0
★
Group b1: Start and Stop Control Parameters
b1-00 Start mode
0: Direct start
1: Rotational speed tracking restart
2: Pre-excited start (AC asynchronous motor)
0
★
b1-01
Rotational speed tracking
mode
0: From frequency at stop
1: From zero speed
2: From maximum frequency
0
★
b1-02
Rotational speed tracking
ratio
1~100
20
★
b1-03 Startup frequency
0.00~10.00 Hz
0.00 Hz
☆
b1-04
Startup frequency holding
time
0.0s~100.0s
0.0s
★
b1-05
Startup DC braking
current/ Pre-excited
current
0%~100%
0%
★
b1-06
Startup DC braking time/
Pre-excited time
0.0s~100.0s
0.0s
★
b1-07 Stop mode
0: Decelerate to stop
1: free stop