Appendix II
EM12 User’s Manual
146
Code
Parameter Name
Setting range
Default
Property
bb-09 Fault auto reset times
0~99
0
☆
bb-10
Relay action selection
during fault auto reset
0: Not act
1: Act
0
☆
bb-11
Time interval of fault auto
reset
0.1s~100.0s
1.0s
☆
bb-12
Input phase loss
protection/contactor
energizing protection
selection
Unit's digit: Input phase loss protection
0: Disabled
1: Enabled
Ten's digit: Contactor energizing protection
0,1( same as Unit’s digit)
11
☆
bb-13
Output phase loss
protection
0: Disabled
1: Enabled
1
☆
bb-14 Off load protection
0: Disabled
1: Enabled
0
☆
bb-15 Off load detection level
0.0%~100.0% (rated motor current)
10.0%
☆
bb-16 Off load detection time
0.0s~60.0s
1.0s
☆
bb-17
Over-speed detection
value
0.0%~50.0% (maximum frequency)
20.0%
☆
bb-18 Over-speed detection time 0.0s~60.0s
1.0s
☆
bb-19
Detection value of too
large speed deviation
0.0%~50.0% (maximum frequency)
20.0%
☆
bb-20
Detection time of too large
speed deviation
0.0s~60.0s
5.0s
☆
bb-21
Action selection at
instantaneous power
failure
0: Invalid
1: Decelerate
2: Decelerate to stop
0
☆
bb-22
Judging voltage of
instantaneous power
failure restoring
60.0%
~
100.0%(standard bus voltage)
90.0%
☆
bb-23
judging time of
Instantaneous power rise
0.00s
~
100.00s
0.50s
☆
bb-24
Judging voltage of
instantaneous power
failure
60.0%~100.0% (standard bus voltage)
80.0%
☆
bb-25
Type of motor temperature
sensor
0: No temperature sensor
1: PT100
2: PT1000
0
☆
bb-26
Motor overheat protection
threshold
0°C~200°C
110°C
☆
bb-27
Motor overheat
pre-warning threshold
0°C~200°C
90°C
☆
bb-28 Overvoltage threshold
200.0~2500.0 V
810V
☆
bb-29 Under voltage threshold
50.0%~150.0%
100.0%
☆
bb-30 Brake unit use ratio
0%~100%
100%
☆
bb-31 Rapid current limit
0: Disabled
1: Enabled
1
☆