Appendix II
EM12 User’s Manual
130
Code
Parameter Name
Setting range
Default
Property
b0-07 Frequency source selection
Unit's digit: Frequency source selection.
0: Main frequency source X
1: X and Y calculation (calculation result determined
by ten's digit)
2: Switchover between X and Y
3: Switchover between X and "X and Y calculation"
4: Switchover between Y and "X and Y calculation"
Ten's digit: X and Y calculation relationship
0: X+Y
1: X-Y
2: Maximum of them
3: Minimum of them
0
☆
b0-08
Frequency offset of
auxiliary frequency source
of X and Y
0.00 Hz ~ maximum frequency(b0-13)
0.00 Hz
☆
b0-09
Binding command source
to frequency source
Unit's digit: Binding keypad command to following
frequency source.
0: No binding
1: Frequency source by digital setting
2: AI1
3: AI2
4: AI3
5: Pulse setting (HDI)
6: Multi-function
7: Simple PLC
8: PID
9: Communication setting
Ten's digit: Binding terminal command to frequency
source.
0~9, same as unit's digit
Hundred's digit: Binding communication command to
frequency source.
0~9, same as unit's digit
Thousand’s digit: Automatically running binding to
frequency source.
0~9, same as unit's digit
0
☆
b0-10
Record of digital setting
frequency of power failure
0: not record
1:record
0
☆
b0-11 Frequency unit
1: 0.1 Hz
2: 0.01 Hz
2
☆
b0-12 Preset frequency
0.00 ~ maximum frequency (b0-13)
50.00 Hz
☆
b0-13 Maximum frequency
50.00~3000.00 Hz
50.00 Hz
☆
b0-14
Source of frequency upper
limit
0: Set by (b0-15)
1: AI1
2: AI2
3: AI3
4: Pulse setting (HDI)
5: Communication setting
0
☆