SLX.Er
Solutions Module slot X trip: Solutions Module in slot X has detected a fault
202,207,212
SLM module category
Check value in Pr
15
/
16
/
17.50
. The following table lists the possible error codes for the SM-SLM. See the
Diagnostics
section in the
SM-SLM User Guide
for more information.
SLX.HF
Solutions Module slot X trip: Solutions Module X hardware fault
200,205,210
Ensure Solutions Module is installed correctly
Return Solutions Module to supplier
SL3.HF
Building automation interface: Module hardware fault
210,210
Ensure Solutions Module is installed correctly
Return Solutions Module to supplier
SLX.nF
Solutions Module slot X trip: Solutions Module has been removed
203,208,213
Ensure Solutions Module is installed correctly
Reinstall Solutions Module
Save parameters and reset drive
SL3.nF
Building automation interface: Module has been removed
213,213
Ensure Solutions Module is installed correctly
Reinstall Solutions Module
Save parameters and reset drive
SL.rtd
Solutions Module trip: Drive mode has changed and Solutions Module parameter routing is now incorrect
215
Press reset.
If the trip persists, contact the supplier of the drive.
SLX.tO
Solutions Module slot X trip: Solutions Module watchdog timeout
201,206,211
Press reset.
If the trip persists, contact the supplier of the drive.
SL3.tO
Building automation interface: Module watchdog timeout
211,211
Press reset.
If the trip persists, contact the supplier of the drive.
t038
User trip defined in 2
nd
processor Solutions Module code
38
SM-Applications program must be interrogated to find the cause of this trip
t040 to t089
User trip defined in 2
nd
processor Solutions Module code
40 to 89
SM-Applications program must be interrogated to find the cause of this trip
Trip
Diagnosis
Error Code
Trip Description
0
No fault detected
1
Power supply overloaded
2
SLM version is too low
3
DriveLink error
4
Incorrect switching frequency selected
5
Feedback source selection incorrect
6
Encoder error
7
Motor object number of instances error
8
Motor object list version error
9
Performance object number of instances error
10
Parameter channel error
11
Drive operating mode incompatible
12
Error writing to the SLM EEPROM
13
Motor object type incorrect
14
Unidrive SP object error
15
Encoder object CRC error
16
Motor object CRC error
17
Performance object CRC error
18
Unidrive SP object CRC error
19
Sequencer timeout
74
Solutions module over temperature