Safety
Information
Introduction
Product
Information
System
configuration
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
Onboard
PLC
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
246
Unidrive SPM User Guide
www.controltechniques.com Issue Number: 3
SM-LON parameters
Parameter
Range(
Ú
)
Default(
Ö
)
Type
x.01
Solutions Module ID
0 to 599
401
RO Uni
PT US
x.02
Solutions Module software version
0.00 to 99.99
RO Uni
NC PT
x.03
Node ID
0 to 127
0
RW Uni
x.06
Option module diagnostic information
-9999 to 9999
0
RW Uni
x.07
Network loss trip
0 to 1
0
RW Uni
x.10
Subnet ID
0 to 255
0
RW Uni
x.11
Domain ID length
0 to 6
0
RW Uni
x.12
Domain ID byte 1
0 to 255
0
RW Uni
x.13
Domain ID byte 2
0 to 255
0
RW Uni
x.14
Domain ID byte 3
0 to 255
0
RW Uni
x.15
Domain ID byte 4
0 to 255
0
RW Uni
x.16
Domain ID byte 5
0 to 255
0
RW Uni
x.17
Domain ID byte 6
0 to 255
0
RW Uni
x.30
Load Option Defaults
Off (0) or On (1)
Off (0)
RW Bit
x.31
Save option parameters
Off (0) or On (1)
Off (0)
RW Bit
x.32
Request to re-initialise
Off (0) or On (1)
Off (0)
RW Bit
x.33
Restore parameters from option
module
Off (0) or On (1)
Off (0)
RW Bit
x.34
Initialise drive reference selectors
Off (0) or On (1)
Off (0)
RW Bit
x.35
Option module serial number
-
2147483648 to 2147483647
RO Bi
NC PT
x.36
Transmit service pin message
Off (0) or On (1)
Off (0)
RW Bit
x.37
Wink active
Off (0) or On (1)
Off (0)
RW Bit
x.38
Unconfigure option module
0 to 1
0
RW Uni
x.39
Default configuration property storage
0 to 1
0
RW Uni
x.50
Module error status
0 to 255
RO Uni
NC PT
x.51
Module software sub-version
0 to 99
RO Uni
NC PT
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not copied
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save