Table 9-3 Menu 3 Regen parameter descriptions
Figure 9-2 Current trimming state diagram
The power (Pr
5.03
) and the reactive power are the power or VAR's respectively that flow from the supply to the drive. Therefore when this parameter
is positive the phase current flowing from the supply to the drive contains a component that lags the respective phase voltage, and when this
parameter is negative the phase current contains a component which leads the respective phase voltage at the drive terminals.
Parameter
Range(
Ú
)
Default(
Ö
)
Type
3.01
Reactive power
±POWER_MAX kVAR’s
RO Bi
FI NC PT
3.02
Input inductance
0.000 to 500.000 mH
RO Uni
NC PT
3.03
Regen drive status
0 to 15
RO Uni
NC PT
3.04
Regen restart mode
0 to 2
1
RW Uni
US
3.05
Voltage setpoint
0 to DC_VOLTAGE_SET_MAX V
700 Vdc
RW Uni
US
3.06
Voltage controller Kp gain
0 to 65535
4000
RW Bi
US
3.07
Close start up contactor
OFF (0) or On (1)
RO Uni
NC
3.08
Main contactor closed
OFF (0) or On (1)
0
RO Uni
NC
3.09
Enable motor drive
OFF (0) or On (1)
RO Uni
NC
3.10
Power feed forward compensation
±100.0 %
0.0
RW Bi
NC
3.11
Current trimming mode
0 to 1
0
RW Uni
US
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not cloned
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save
3.01
Reactive power
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
2
1
1
1
Range
Regen
±POWER_MAX kVAR’s
Update rate
Background
Mains Loss
Current Trim
Close Main Contactor
Waiting for Enable
Open Contactor
Current Trim
Close Main Contactor
Active
(not synchronised)
Synchronied
Disabled
Disabled
Enabled Pr
3
.
11
= 0
Synchronised
Contactor 100ms delay
Trim complete
Contactor open + 100ms delay
Enabled (Pr
3
.
11
= 1)
Contactor 100ms delay
Trim complete
Supply o.k
Mains loss or contactor open
when it should be closed