Unidrive SP Regen Installation Guide
www.controltechniques.com Issue Number: 2
At power-up this parameter is zero. Each time the Regen drive is enabled the supply inductance is measured and displayed by this parameter. The
value given is only approximate, but will give an indication as whether the input inductance is correct for the sinusoidal rectifier unit size. The
measured value should include the supply inductance as well as the Regen drive input inductance, however, the supply filter capacitance, masks the
effect of the supply inductance. Therefore the value measured is usually the Regen drive input inductor value.
If an L.Sync trip occurs Pr
3.03
indicates the reason. At power-up and on trip reset this parameter is set to zero. Once an L.Sync trip has occurred this
parameter shows when the trip occurred and the reason for the last L.Sync trip as indicated by the bits in the table below. The reasons for the trip are
either because the supply frequency is out of range or the PLL (phase lock loop) within the drive cannot synchronise to the supply waveforms.
Pr
3.04
defines the action taken after enable and when a synchronisation failure occurs.
0, rESYnC:
Continuously attempt to re-synchronise
1, del.triP:
delayed trip
Attempt to synchronise for 30s. If unsuccessful after this time then give a LI.SYnC trip. After a failure during running attempt to re-synchronise for 30s
before tripping.
2, triP:
immediate trip
Attempt to synchronise for 30s. If unsuccessful after this time then give a LI.SYnC trip. After a failure during running, trip immediately.
3.02
Input inductance
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
3
1
1
1
1
Range
Regen
0.000 to 500.000mH
Update rate
Background
3.03
Regen status
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
Regen
0 to 15
Update rate
4ms
Bit
Status
0
Tripped during synchronisation
1
Tripped while running
2
Reason for trip was supply frequency <30.0Hz
3
Reason for trip was supply frequency >100.0Hz
4
Reason for trip was PLL could not be synchronised
3.04
Regen restart mode
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
Regen
0 to 2
Default
Regen
1
Update rate
Background