Safety
Information
Introduction
Product
information
System
design
Mechanical
installation
Electrical
installation
Getting
started
Optimisation
Parameters
Technical
data
Component
sizing
Diagnostics
108
Unidrive SP Regen Installation Guide
www.controltechniques.com Issue Number: 2
Table 9-5 Menu 5 Regen parameter descriptions
In Regen mode the supply frequency is shown. Negative values indicate negative phase rotation of the supply.
This is the modulus of the r.m.s. fundamental line to line voltage at the inverter output.
The output power is the dot product of the output voltage and current vectors. Positive power indicates power flowing from the supply to the drive, and
negative power indicates power flowing from the drive to the supply.
Voltage across the internal DC bus of the drive.
Parameter
Range(
Ú
)
Default(
Ö
)
Type
5.01
Output / supply frequency
±100.0 Hz
RO Bi
FI NC PT
5.02
Output / supply voltage
0 to AC_VOLTAGE_MAX V
RO Uni FI NC PT
5.03
Output / supply power
±POWER_MAX kW
RO Bi
FI NC PT
5.05
DC bus voltage
0 to +DC_VOLTAGE_MAX V
RO Uni FI NC PT
5.07
Regen drive rated current
0 to RATED_CURRENT_MAX A
RW Uni
US
5.18
Maximum switching frequency
0 to 5 (3, 4, 6, 8, 12, 16 kHz)
0
RW Uni
US
5.35
Disable auto-switching frequency
0 to 1
0
RW Uni
US
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not cloned
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save
5.01
Supply frequency
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
Regen
±100.0 Hz
Update rate
250
µ
s
5.02
Supply voltage
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
Regen
0 to AC_VOLTAGE_MAX V
Update rate
Background
5.03
Supply power
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV PT
US RW BU PS
1
1
2
1
1
1
Range
Regen
±POWER_MAX kW
Update rate
Background
5.05
DC bus voltage
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU PS
1
1
1
1
1
1
Range
Regen
0 to +DC_VOLTAGE_MAX V
Update rate
Background
Содержание SP1201
Страница 219: ......