Figure D-7: Signal Quality Alert
%
'
$
(
&
)
*
A. Signal quality
B. Time
C. Alert ON
D. Deadband
E. Limit
F. The Signal Quality drops below the alert limit and an alert message is triggered.
G. The alert message is reset once the Signal Quality value rises above the Deadband range.
Limit
The Signal Quality value that will trigger the alert.
Deadband
The Deadband is a buffer zone so the alerts do not toggle on and off when the Signal
Quality fluctuates around the alert limit. The alert is set when value falls below the alert
limit. The alert is then cleared when value rises above the Deadband range.
High/low level alerts
High/Low Level Alerts are triggered when the level goes outside the user defined Limits.
There are four standard Level Alerts. Hi Level Alert and Hi-Hi Level Alert are used for rising
levels, and Lo Level Alert and Lo-Lo Level Alert are used for falling levels. See
and
Configuration parameters
Reference Manual
February 2020
00809-0100-4308
216
Rosemount 3308 Series
Содержание Rosemount 3308A
Страница 8: ...Contents Reference Manual February 2020 00809 0100 4308 viii Rosemount 3308 Series ...
Страница 10: ...Introduction Reference Manual February 2020 00809 0100 4308 10 Rosemount 3308 Series ...
Страница 22: ...Transmitter overview Reference Manual February 2020 00809 0100 4308 22 Rosemount 3308 Series ...
Страница 74: ...Installation Reference Manual February 2020 00809 0100 4308 74 Rosemount 3308 Series ...
Страница 96: ...Configuration Reference Manual February 2020 00809 0100 4308 96 Rosemount 3308 Series ...
Страница 194: ...Product Certifications Reference Manual February 2020 00809 0100 4308 194 Rosemount 3308 Series ...
Страница 222: ...Configuration parameters Reference Manual February 2020 00809 0100 4308 222 Rosemount 3308 Series ...