background image

Datasheet

The Sure Cross

®

 wireless system is a radio frequency network with integrated I/O that operates in most environments to eliminate the need for

wiring runs. Wireless MultiHop data radio networks are formed around a MultiHop master and one or more slaves and extend the range of a Modbus

or other serial communication network.

• Wireless industrial I/O device with four thermocouple inputs, two NPN discrete inputs, one thermistor

input, and two NMOS discrete outputs

FlexPower

®

 power options allow for 10 to 30 V dc, solar, and battery power sources for low power

applications.

• Self-healing, auto-routing RF network with multiple hops extends the network’s range

• Serial and I/O communication on a Modbus platform

• Message routing improves link performance

• DIP switches select operational modes: master, repeater, or slave

• Built-in site survey mode enables rapid assessment of a location’s RF transmission properties

• Frequency Hopping Spread Spectrum (FHSS) technology ensures reliable data delivery within the

unlicensed Industrial, Scientific, and Medical (ISM) band

For additional information, updated documentation, and a list of accessories, refer to Banner Engineering's website, 

www.bannerengineering.com/

wireless

.

WARNING:

• Do not use this device for personnel protection
• Using this device for personnel protection could result in serious injury or death.
• This device does not include the self-checking redundant circuitry necessary to allow its use in personnel safety

applications. A device failure or malfunction can cause either an energized (on) or de-energized (off) output condition.

Important:

• Electrostatic discharge (ESD) sensitive device
• ESD can damage the device. Damage from inappropriate handling is not covered by warranty.
• Use proper handling procedures to prevent ESD damage. Proper handling procedures include leaving devices in their

anti-static packaging until ready for use; wearing anti-static wrist straps; and assembling units on a grounded, static-
dissipative surface.

Models

Models

Frequency

Power

Housing

I/O

DX80DR2M-H3E-NB-KR

2.4 GHz ISM Band

10 to 30 V dc or
integrated battery (ships
without the battery)

IEC IP65; NEMA 4X

Inputs: Two NPN discrete, four thermocouple, one thermistor
(internal)
Outputs: Two NMOS discrete
Serial interface: RS-232

Configuration Instructions

Setting Up Your MultiHop Network

To set up and install your wireless MultiHop network, follow these steps:

1. If your radios have DIP switches, configure the DIP switches of all devices.
2. Connect the sensors to the MultiHop radios if applicable.
3. Apply power to all devices.
4. If your MultiHop radio has rotary dials, set the MultiHop Radio (Slave) ID. If your MultiHop radio has no rotary dials, continue to the next

step.

5. Form the wireless network by binding the slave and repeater radios to the master radio. If the binding instructions are not included in this

datasheet, refer to the quick start guide or product manual.

6. Observe the LED behavior to verify the devices are communicating with each other.
7. Configure any I/O points to use the sensors connected to the Sure Cross devices.
8. Conduct a site survey between the MultiHop radios. If the site survey instructions are not included in this datasheet, refer to the product

manual.

Sure Cross

®

 MultiHop H3E-NB-KR Data Radio

 

 

Original Document

209529 Rev. A

18 January 2019

209529

Содержание Sure Cross MultiHop H3E-NB-KR

Страница 1: ...ergized off output condition Important Electrostatic discharge ESD sensitive device ESD can damage the device Damage from inappropriate handling is not covered by warranty Use proper handling procedures to prevent ESD damage Proper handling procedures include leaving devices in their anti static packaging until ready for use wearing anti static wrist straps and assembling units on a grounded stati...

Страница 2: ...and enable the receiver slots select for switches 1 2 ON ON Transmit power 900 MHz radios 1 00 Watt 30 dBm 2 4 GHz radios 0 065 Watts 18 dBm and 60 ms frame OFF Transmit power 900 MHz radios 0 25 Watts 24 dBm 2 4 GHz radios 0 065 Watts 18 dBm and 40 ms frame ON Application mode Modbus OFF Application mode Transparent ON MultiHop radio setting Repeater OFF OFF MultiHop radio setting Master OFF ON M...

Страница 3: ...nected to the BAT terminal When powering the device from the integrated battery the BAT connection must remain open Integrated battery RS 485 for P1E M H1E M H12E and P16E Models Integrated battery RS 232 for P3E P4E M H3E and M H4E Models 1 2 3 4 BAT 1 10 V dc to 30 V dc optional 10 V dc to 30 V dc optional 2 RS 485 D1 B RS 232 Tx 3 dc common GND dc common GND 4 RS 485 D0 A RS 232 Rx Terminal Blo...

Страница 4: ...an RS 485 to USB adapter cable with a wall plug that can power your 1 Watt MultiHop radio while you configure it The adapter cable is not required when connecting to a DXM Controller Download the most recent software revision from the Wireless Reference Library on Banner Engineering s website www bannerengineering com Installing Your Sure Cross Radios Please refer to one of the following instructi...

Страница 5: ...t configuration is set to a Type B thermocouple 0 Value Thermocouple Type Value Thermocouple Type Value Thermocouple Type 0 B 5 J 10 P 1 C 6 K 11 R 2 D 7 L 12 S 3 E 8 M 13 T 4 G 9 N 14 U Modbus Addressing Convention All Modbus addresses refer to Modbus holding registers When writing your own Modbus scripts use the appropriate commands for interfacing to holding registers Parameter description head...

Страница 6: ...s these are a fire explosion and severe burn hazard Do not burn or expose them to high temperatures Do not recharge crush disassemble or expose the contents to water For hazardous or non hazardous locations the replacement battery model number is BWA BATT 001 Xeno model number XL 205F For non hazardous locations only the replacement battery model number is BWA BATT 011 For pricing and availability...

Страница 7: ...ckel finish PVC insulation 3 2 35 mm 6 mm 4 20 mm 72 mm Tube Included with the DX80 E Models Mounting hardware kit BWA HW 003 PTFE tape BWA 9O2 C 900 MHz or BWA 2O2 C 2 4 GHz Antenna 2 dBd Omni Rubber Swivel RP SMA Male Not included with Internal antenna models BWA BATT 001 Replacement battery 3 6 Volt D Lithium Cell BWA HW 032 Access Hardware for E Housing One each of 1 2 inch plug 1 2 inch gland...

Страница 8: ...NTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT WHETHER ARISING IN CONTRACT OR WARRANTY STATUTE TORT STRICT LIABILITY NEGLIGENCE OR OTHERWISE Banner Engineering Corp reserves the right to change modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Ban...