Table A-1: Maximum Recommended Viscosity and Contamination/Build-up
Probe type
Maximum viscosity
Contamination/build-up
Single lead
Build-up allowed
Twin lead
1500 cP
Thin build-up allowed, but no
bridging
Coaxial
500 cP
Not recommended
(1)
Consult your local Emerson representative in the case of agitation/turbulence and high viscous
products.
A.1.4
Measuring range
Table A-2: Measuring Range and Minimum Dielectric Constant
Probe type
Maximum measuring range
Flexible single lead
55.8 ft. (17 m)
2.0, when distance < 32.8 ft. (10 m)
10, when distance > 32.8 ft. (10 m)
Rigid single lead probe (0.3-in./8 mm)
9.8 ft. (3 m)
2.0
Rigid single lead probe (0.5-in./13 mm)
19.7 ft. (6 m)
2.0
Segmented rigid single lead
32.8 ft. (10 m)
2.0
Flexible twin lead
55.8 ft. (17 m)
2.0, when distance < 32.8 ft. (10 m)
10, when distance > 32.8 ft. (10 m)
Coaxial
19.7 ft. (6 m)
2.0
(1)
Minimum Dielectric Constant may be lower than 2.0 if one or more of the following conditions apply:
•
Probe is installed in stilling well or chamber.
•
Maximum measuring range is not utilized.
•
Noise Threshold is manually adjusted to a lower level.
Interface measuring range
The maximum allowable upper product thickness/measuring range is primarily
determined by the dielectric constants of the two liquids.
Typical applications include interfaces between oil/oil-like and water/water-like liquids,
with a low (<3) dielectric constant for the upper product and a high (>20) dielectric
constant for the lower product. For such applications, the maximum measuring range is
limited by the length of the coaxial and rigid single lead probes.
For flexible probes, the maximum measuring range is reduced by the maximum upper
product thickness, according to the diagram below. However, characteristics may vary
between the different applications.
Reference Manual
Specifications and reference data
00809-0100-4308
February 2020
Reference Manual
143
Содержание Rosemount 3308A
Страница 8: ...Contents Reference Manual February 2020 00809 0100 4308 viii Rosemount 3308 Series ...
Страница 10: ...Introduction Reference Manual February 2020 00809 0100 4308 10 Rosemount 3308 Series ...
Страница 22: ...Transmitter overview Reference Manual February 2020 00809 0100 4308 22 Rosemount 3308 Series ...
Страница 74: ...Installation Reference Manual February 2020 00809 0100 4308 74 Rosemount 3308 Series ...
Страница 96: ...Configuration Reference Manual February 2020 00809 0100 4308 96 Rosemount 3308 Series ...
Страница 194: ...Product Certifications Reference Manual February 2020 00809 0100 4308 194 Rosemount 3308 Series ...
Страница 222: ...Configuration parameters Reference Manual February 2020 00809 0100 4308 222 Rosemount 3308 Series ...