determine the alarm priorities assigned to each status signal category by your host.
Manual configuration may be required. DeltaV assigns a priority of two or higher. The
priority is based on status signal category. The status signal priority determines the
behavior of both real and simulated alerts.
2.6.4
Plantweb alerts overview
Alerts are generated, mapped, and masked as NE 107 Status Signals. If Plantweb
™
alerts
are required the NE 107 Status Signals are automatically converted to Plantweb alerts for
annunciation and display. Plantweb alerts have three alert parameters. They are in order
from highest to lowest priority:
1. FAILED_ALM
2. MAINT_ALM
3. ADVISE_ALM
The eight alert conditions are factory configured to annunciate as one of the three specific
alert parameters.
Plantweb alert parameter conditions and factory defaults
Emerson ships devices from the factory with all applicable Plantweb
™
alerts enabled. The
alert conditions reported in each parameter are:
1. FAILED_ALM
a. Incompatible module
b. Sensor failure
c. Electronics failure
A FAILED_ALM indicates a failure within a device that will make the device or some
part of the device non-operational. This implies that the process variable may no
longer be available and the device is in need of immediate repair.
2. MAINT_ALM
a. Pressure out of limits
b. Sensor temperature out of limits
A MAINT_ALM indicates that the device is experiencing pressure or temperature
conditions that are outside the device operating range. This implies that the
process variable may no longer be accurate. It also implies that if the condition is
ignored the device will eventually fail. The device should be checked to determine
the type of abnormal condition and recommended actions to resolve it.
3. ADVISE_ALM
a. Function check
b. Display update failure
c. Variation change detected
An ADVISE_ALM indicates a transducer block is not in Auto mode. This may be due to
configuration or maintenance activities. It can also indicate an abnormal process or device
Configuration
Reference Manual
July 2020
00809-0100-4774
32
Rosemount 3051
Содержание Rosemount 3051 CF Series
Страница 4: ...4 ...
Страница 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Страница 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Страница 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Страница 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Страница 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Страница 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...