Continuously connected throughout the segment
•
Connected to a good earth ground at the power supply end
Figure 4-3: Wiring Terminals
A. Minimize distance.
B. Trim shield and insulate.
C. Protective grounding terminal (do not ground cable shield at the transmitter).
D. Insulate shield.
E. Minimize distance.
F. Connect shield back to the power supply ground.
Perform the following procedure to make wiring connections:
Procedure
1. Remove the housing cover on terminal compartment side. Do not remove the
cover in explosive atmospheres when the circuit is live. Signal wiring supplies all
power to the transmitter.
2. Ensure full contact with terminal block screw and washer. When using a direct
wiring method, wrap wire clockwise to ensure it is in place when tightening the
terminal block screw.
Note
Emerson does not recommend using a pin or ferrule wire terminal, as the
connection may be more susceptible to loosening over time or under vibration.
3. Plug and seal the unused conduit connection on the transmitter housing to avoid
moisture accumulation in the terminal side. Install wiring with a drip loop. Arrange
Electrical installation
Reference Manual
July 2020
00809-0100-4774
88
Rosemount 3051
Содержание Rosemount 3051 CF Series
Страница 4: ...4 ...
Страница 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Страница 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Страница 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Страница 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Страница 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Страница 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...