Figure 4-2: Conduit Installation Diagrams
A
A
B
B
A. Possible conduit line positions
B. Sealing compound
4.5.2
Power supply for F
OUNDATION
™
Fieldbus
Power supply
The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic safety and 9 and
17.5 Vdc for FISCO intrinsic safety) to operate and provide complete functionality.
Power conditioner
A Fieldbus segment requires a power conditioner to isolate the power supply filter and
decouple the segment from other segments attached to the same power supply.
4.6
Wiring
4.6.1
Transmitter wiring
Wiring and power supply requirements can be dependent upon the approval certification.
As with all F
OUNDATION
™
Fieldbus requirements, a conditioned power supply and
terminating resistors are required for proper operation.
displays the standard
Rosemount 3051 terminal block. The terminals are not polarity sensitive. The transmitter
requires 9–32 Vdc to operate. Emerson recommends Type A FOUNDATION Fieldbus
wiring 18 awg twisted shielded pair. Do not exceed 5000 ft. (1500 m) total segment
length.
Note
Avoid running instrument cable next to power cables in cable trays or near heavy electrical
equipment.
Note
It is important that the instrument cable shield be:
•
Trimmed close and insulated from touching the transmitter housing
Reference Manual
Electrical installation
00809-0100-4774
July 2020
Reference Manual
87
Содержание Rosemount 3051 CF Series
Страница 4: ...4 ...
Страница 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Страница 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Страница 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Страница 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Страница 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Страница 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...