3.5.4
Inline process connection
Inline gage transmitter orientation
CAUTION
Erroneous pressure values
The transmitter may output erroneous pressure values.
Do not interfere or block the atmospheric reference port.
The low side pressure port on the inline gage transmitter is located in the neck of the
transmitter, behind the housing. The vent path is 360 degrees around the transmitter
between the housing and sensor (see
).
Keep the vent path free of any obstruction, such as paint, dust, and lubrication, by
mounting the transmitter so that the process can drain away.
Figure 3-11: Inline Gage Low Side Pressure Port
A
A. Low side pressure port (atmospheric reference)
CAUTION
Electronics damage
Rotation between the sensor module and the process connection can damage the
electronics.
Do not apply torque directly to the sensor module.
To avoid damage, apply torque only to the hex-shaped process connection.
Hardware installation
Reference Manual
July 2020
00809-0100-4774
70
Rosemount 3051
Содержание Rosemount 3051 CF Series