RSTi-OM User Manual
Section 7
GFK-3212A
Jun 2021
Configuring IO-Link Devices
68
The IO-Link Device Port table provides detailed information about the indexes and sub-indexes. Not
all indexes have sub-indexes.
Figure 48: IO-Link Device Port Table
o
o
If the IODD file follows IO-Link specifications, an asterisk next to RW means that parameter is
not included in Data Storage.
o
If a Sub-index has an asterisk next to it in the GUI, that means that sub-index is not sub-
indexable. This may be useful information when using the IO-Link Device ISDU Interface or
programming your PLC.
This example shows that Index 21.
When you perform a GET on Index 21 using the ISDU Interface, these are the results:
Figure 49: Get command on Index 21
The GUI displays this information about Index 21.
Figure 50: Index 21 Information