Connecting the Power
The IOLM provides M12 (5-poles) L-coded input and output power connectors. Use a 24VDC power
supply capable of the total output current required.
Note: Power connectors must have an approved cable or protective cover attached to the port
guarantee to IP67 compliance. If you require cables or protective covers, see the Emerson website.
Figure 5: IOLM Power Connectors Pinout
Pin
Power Input
(Male)
Power Output or Actuator
Power (Female)
Description
1
V
S
+
V
S
+ or +V
IO-
Link Master’s system electronics and IO
-
Link devices
2
V
A
-
V
A
- or 0V
Actuator supply
3
V
S
-
V
S
- or 0V
IO-
Link Master’s system electronics and IO
-
Link devices
4
V
A
+
V
A
+ or +V
Actuator supply
5
FE
Note: The IOLM requires a UL-listed power supply with an output rating of 24VDC.
Power Supply
Values
Power Supply In - Maximum V
S and
V
A
16A (Maximum)
IO-Link Connector
Port 1
C/Q (Pin 4)
L+/L- Sensor Supply (Pins 1 and 3)
200 mA (Maximum) 1.6 A (Maximum)
IO-Link Connector
Port 3
C/Q (Pin 4)
L+/L- Sensor Supply (Pins 1 and 3)
200 mA (Maximum) 1 A (Maximum)
IO-Link Connectors Ports 2 and 4 - 8
C/Q (Pin 4)
L+/L- Sensor Supply (Pins 1 and 3)
200 mA (Maximum)
500 mA (Maximum)/up to 1A Output Budget
Note: See
information about how to divide up the power
output between ports.
IOLM Power
100 mA @ 24 VDC (U
S
)
Power Supply Out
V
S
V
A
16A
†
(Maximum)
16A
††
(Maximum)
†
V
S
output available is determined by subtracting the following from the available input
current.
IO-Link Master module electronics current.
Total L+/L- current for all IO-Link ports.
Total C/Q current for all IO-Link ports.
††
V
A
output available is the same as the available U
A
input current.
You can use the following procedure to connect the IOLM to a power supply.
Note: Power should be disconnected from the power supply before connecting it to the IOLM.
Otherwise, your screwdriver blade can inadvertently short your power supply terminal connections to
the grounded enclosure.