112
Micro Motion
®
Model 3711 Gas Flow Computers
Function Sequence Tables
Two examples of FST functions are shown below. These functions are executed sequentially.
In the first function, the VAL command writes the current process value (in EUs) of an analog input to
the implied Result Register. The label is used only for identification.
In the second function, when the RR value from Step 0 equals or exceeds the High Alarm value, the
FST branches to the PUMPON function to turn the pump on.
Step 2
Specify FST register values
This step is required only if your FST requires startup floating-point values.
1. Click
Configure > Control > FST Register
. The window shown in Figure 11-3 is displayed.
2. Use the dropdown list to select the FST for which you are defining registers.
3. Enter any required startup values for the FST. Parameters are listed and described in
Table 11-1.
Figure 11-3
FST Registers – General panel
STEP
LABEL
CMD
ARGUMENT1
ARGUMENT2
0
CKHIAL
VAL
AIN 3-1, EU
1
>=
AIN 3-1, HIAL
PUMPON
Содержание Micro Motion 3711
Страница 32: ...24 Micro Motion Model 3711 Gas Flow Computers ...
Страница 44: ...36 Micro Motion Model 3711 Gas Flow Computers ...
Страница 56: ...48 Micro Motion Model 3711 Gas Flow Computers ...
Страница 68: ...60 Micro Motion Model 3711 Gas Flow Computers ...
Страница 92: ...84 Micro Motion Model 3711 Gas Flow Computers ...
Страница 108: ...100 Micro Motion Model 3711 Gas Flow Computers ...
Страница 140: ...132 Micro Motion Model 3711 Gas Flow Computers ...
Страница 196: ...188 Micro Motion Model 3711 Gas Flow Computers ...
Страница 210: ...202 Micro Motion Model 3711 Gas Flow Computers ...
Страница 233: ......