Chapter 8 Troubleshooting 69
Liebert. PEX+Series Precision Air Conditioner User Manual
Chapter 8 Troubleshooting
This chapter introduces the troubleshooting.
warning
!
Certain circuits carry lethal voltages. Only professional technicians are allowed to maintain the unit. Extra care
should be taken when troubleshooting online.
Note
If jumpers are used for troubleshooting, remember to remove the jumpers after the troubleshooting, or the
connected jumpers may bypass certain control function and damage the equipment.
8.1 Fan Troubleshooting
The troubleshooting of fan is listed in Table 8-1.
Table 8-1 Fan fault removal
Symptom
Potential causes
Items to be examined or handled
FC fan cannot
be started
No main power supply
Examine the rated voltage of L1, L2 and L3 of the fan
Circuit breaker
disconnection
Examine the circuit breaker of main fan
Overload, circuit breaker
disconnection
Manual reset. Examine the current value
Contactor not pulling on
Examine whether there is 24Vac voltage between P36-3 and E1. If there is, but
the contactor cannot pull on, then the contactor has failures. Please replace the
contactor
Control board failure
Examine whether there is 24Vac voltage between P36-3 and E1. If there is not,
then the control panel has failures. Please check whether the green LED beside
silicon control Q5 on the control panel is on or not
Fuse panel failure
Examine whether there is 24Vac voltage between P36-3 and E1. If there is not,
and the green LED beside Q5 is not on, please check further whether LED DS4
beside F4 on the fuse panel is on, or take down F4 to test whether it is burnt out
Air flow loss switch alarm
(action)
1) Check that the belt is firm and the fan motor is normal;
2) Check whether the external static pressure (ESP) is too high, if so, fix it by
optimizing the air channel and adjusting the belt setting value properly
The fan is ineffective
Replace the fan
EC fan cannot
be started
Circuit breaker
disconnection
Examine the circuit breaker of main fan
Contactor cannot close
Examine whether there is 24Vac voltage between P36-3 and E1. If there is, but
the contactor cannot close, then the contactor has failures. Please replace the
contactor
Control board failure
Examine whether there is 24Vac voltage between P36-3 and E1. If there is not,
then the control panel has failures. Please check whether the green LED beside
silicon control Q5 on the control panel is on or not
Fuse panel failure
Examine whether there is 24Vac voltage between P36-3 and E1. If there is not,
and the green LED beside Q5 is not on, please check further whether LED DS4
beside F4 on the fuse panel is on, or take down F4 to test whether it is burnt out
Contactor closed, air flow
lose switch alarm
1) Check whether there is 0 ~ 10Vdc analog signals output from P51, if not,
check the control board carefully;
2) Check whether the values of S147 and S149 are set too low, if so, fix it by
increasing the setting value properly;
3) Check whether the external static pressure (ESP) is too high, if so, fix it by
optimizing the air channel and increasing the setting value properly