48 Chapter 5 iCOM Controller
Liebert. PEX+Series Precision Air Conditioner User Manual
Free-cooling, HG and HW related settings
Table 5-34 Descriptions of free-cooling, HG and HW related settings
Parameters (5/9)
Default
Setting range
Description
A135
K11 ACT
DEH
WNG
、
DEH
、
NOP
、
FC
-
A136
C/W F DUR
3min
1min ~ 3min
Cooling water flush duration
A137
COOL TYP
SINGL
Singl, FC, DC
Three cooling type
A138
STOP FC+
°F
-
Stop FC at set point + or value
A139
FC F DUR
0min
1min ~ 3min
Freecooling flush duration
A140
FC F K11
Yes
Yes, No
Freecooling flush starts R5
A141
COMP + FC
No
Yes, No
Compressor plus FC simultaneously
A142
HW F DUR
3min
0 ~ 3min
Hot water flush duration
A143
HG HEAT
No
Comp.1, Comp.2, No
Hot gas heating enabled
A144
HEAT OP
No
Stage, Delay, No
Electric heater operation mode
A144
HEAT DEH
Dehum
Normal, Dehum
Electric Reheat Operation during Dehum
Humidification and dehumidification related settings
Table 5-35 Descriptions of humidification and dehumidification related settings
Factory 6/9
Default
Setting range
Description
A146
HUM TYPE
IFS
External, IFS, IFL,
PEX6, PEX9, PEX12,
21LLA, 53LLC,
53HLB, 93LLE,
93HLD, d3H, HT2,
HT5, HT9, SGH, No
Humidifier model
A147
HUM VOLT
V
-
-
A148
HUM LAST
15hr
-
Detect whether the last operation time exceeds this cycle
setting during the startup of the humidifier. Unit: hr
A149
PREFILL
30s or 57s
-
Prefill time. Unit: second
A150
FILL
57s
-
Fill time. Unit: second
A151
HUM ON
584s
-
Humidifier on time. Unit: second
A152
DEH COMP
1
1, 2, both
Dehumidification with compressor. When 1 or 2 is selected,
compressor 1 or 2 is used for dehumidification. When Both
is selected, the two compressors are both used for
dehumidification
A153
MAX LL1
26.7°C
5.0-40.0 °C
Max Low Limit 1 Set point
A153
MAX LL2
23.9°C
5.0-40.0 °C
Max Low Limit 2 Set point
Analog output related settings
Table 5-36 Descriptions of analog output related settings
Factory 7/9
Default
Setting range
Description
A157
ANOUT1LO
0%
0-100%
-
A157
ANOUT1HI
100%
0-100%
A158
ANOUT2LO
0%
0-100%
A158
ANOUT2HI
100%
0-100%
A159
ANOUT3LO
0%
0-100%
A159
ANOUT3HI
100%
0-100%
A160
ANOUT4LO
0%
0-100%
A160
ANOUT4HI
100%
0-100%
A161
MIN DEH
100%
0-100%
Min Dehum Fanspeed
A161
MIN HEAT
100%
0-100%
Min Heat Fanspeed
A161
MIN HUM
100%
0-100%
Min Humidifying Fanspeed
A162
FAN MOD
Full
Full,Light
EC-Fan Mode
A163
ANOUT1
No
-
Analog output selection. See Table 5-36
A164
ANOUT2
No
-
A165
ANOUT3
No
-
A166
ANOUT4
No
-