5.7.7 CALIBRATION
The CALIBRATION menu can calibrate sensors by setting offsets. The parameters are listed in Table 5-27. The
parameters are in pairs: the former is the calibrated value and the latter is the calculated value, or the sum of the
measured value and the calibrated value. This value is engaged in the calculation of control need.
Table 5-27 Descriptions of CALIBRATION parameters
Parameters
Default
Description
S602
RTN TEMP
0
Calibrated return air temperature. It can be set as a positive or negative value. Use the UP
and DOWN buttons to change the setting value, 0.1K at each step
S603
CAL TEMP
-
Sum of the calibrated value and measured return air temperature. This value is compared
with the setting value as the system actual temperature and is engaged in the calculation
S604
RTN HUM
+0.0%
Calibrated return air humidity. It can be set as a positive or negative value. Use the UP and
DOWN buttons to change the setting value, 1% at each step
S605
CAL HUM
-
Sum of the calibrated value and measured return air humidity. This value is compared with
the setting value as the system actual humidity and is engaged in the calculation
S606
DS1 NTC
+0.0K
Calibrated digital scroll 1NTC. It can be set as a positive or negative or positive value. Use
the UP and DOWN buttons to change the setting value, 0.1K at each step
S607
CAL DS1
-
Sum of the calibrated value and return air humidity measured by digital scroll 1NTC
sensor. This value is engaged in the calculation
S608
DS2 NTC
+0.0K
Calibrated digital scroll 2NTC. It can be set as a positive or negative value. Use the UP
and DOWN buttons to change the setting value, 0.1K at each step
S609
CAL DS2
-
Sum of the calibrated value and return air humidity measured by digital scroll 2NTC
sensor. This value is engaged in the calculation
S610
OUT SNS
0
Outdoor Sensor
S611
CAL OUT
-
Calibrated Outdoor Sensor
S613
TEMP A1T
+0.0K
Calibrated value of temperature sensor A1T
S614
CAL A1T
-
Calculated value corresponding to temperature sensor A1T
S615
HUM A1H
+0.0%
Calibrated value of humidity sensor A1H
S616
CAL A1H
-
Calculated value corresponding to humidity sensor A1H
S617
TEMP B
TH
Calibrated value of temperature sensor B
S618
TEMP B1T
+0.0K
Type of temperature sensor B1T
S619
CAL B1T
-
Calculated value corresponding to temperature sensor B1T
S620
HUM B2H
+0.0%
Calibrated value of humidity sensor B2H
S621
CAL B2H
-
Calculated value corresponding to humidity sensor B2H
S622
TEMP B2T
+0.0K
Optional Sensor B2T
S62A
CAL B2T
-
Calibrated Optional Sensor B2T
S62B
TYPE C
-
Optional Sensor C Type
S624
FC SNSR
NTC
Free cooling temperature sensor. PTC or NTC sensor can be configured according to the
actual configuration
S625
FC SNSR
+0.0K
Calibrated value of free cooling temperature sensor
S626
CAL FC
-
Calculated value of free cooling temperature sensor
S627
SUP SNSR
NTC
Air supply temperature sensor. PTC or NTC sensor can be configured
S628
SUP TEMP
+0.0K
Calibrated value of air supply temperature sensor
S629
CAL SUP
-
Calculated value of air supply temperature sensor
S630
TEMP C1T
-
Calibrated value of temperature sensor C1T
S630
AMB TEMP
-
Offset Outdoor Temperature
S631
CAL C1T
-
Calculated value of temperature sensor C1T
S631
CAL AMBT
-
Calibrated Outdoor Temperature
S632
HUM C2H
+0.0%
Calibrated value of humidity sensor C2H
S632
AMB HUM
+0.0%
Offset Outdoor Humidity
S633
CAL C2H
-
Calculated value of humidity sensor C
S633
CAL AMBH
-
Calibrated Outdoor Humidity
S63A
TEMP C2T
0
Temperature Sensor C2T Calibration
S63B
CAL C2T
-
Calibrated Optional Sensor C2T