Chapter 5 iCOM Controller 37
Liebert. PEX+Series Precision Air Conditioner User Manual
The WELLNESS menu includes nine groups of parameters, including WELLNESS BASICs, and WELLNESS MOTOR,
WELLNESS COMPs, WELLNESS HEATs and WELLNESS HUM. See Table 5-13 ~ Table 5-22 for detailed parameter
descriptions.
WELLNESS BASIC1
Table 5-13 Descriptions of WELLNESS BASIC1 parameters
Parameters
Default
Setting range
Description
S002
FREQ/YR
1pY
0pY ~ 12pY
Maintenance frequency every year
S003
BONUS
MM
0MM ~ 12MM
Bonus setting
S004
PENALTY
MM
0MM ~ 12MM
Penalty setting
S005
LAST PM
YY
-
Last maintenance. Year (YY), month (MM) and day (DD). This
parameter is read only
S005
LAST PM
MM
S005
LAST PM
DD
WELLNESS BASIC2
Table 5-14 Descriptions of WELLNESS BASIC2 parameters
Parameters
Default
Setting range
Description
S006
SERVICE
-
Name
Service personnel setting
S007
CONFIRM
No
Yes, No
Maintenance confirmation selection
S008
NEXT PM
-
-
Calculated next maintenance. This parameter is read only
WELLNESS MOTOR
Table 5-15 Descriptions of WELLNESS MOTOR parameters
Parameters
Default
Description
S013
STARTS
-
Number of fan starts since the last maintenance
S014
RUN HRS
hr
Fan run hours since the last maintenance
S015
AVG RUN
min
Average fan run time calculated through number of fan starts and run hours
S016
BEST
1
Starts per day best
S017
WORST
24
Starts per day worst
S018
ALARMS
0
Number of alarms since the last maintenance
S019
BONUS
0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS COMP1
Table 5-16 Descriptions of WELLNESS COMP1 parameters
Parameters
Default
Description
S024
STARTS
-
Number of compressor 1 starts since the last maintenance
S025
RUN HRS
hr
Compressor 1 run hours since the last maintenance
S026
AVG RUN
min
Average compressor 1 run time calculated through the number of starts and run hours
S027
BEST
12
Starts per day best
S028
WORST
240
Starts per day worst
S029
HP AL
0
Number of high pressure alarms occurred to compressor 1 since the last maintenance
S030
LP AL
0
Number of low pressure alarms occurred to compressor 1 since the last maintenance
S031
OL AL
0
Number of overload alarms occurred to compressor 1 since the last maintenance
S032
DS HT AL
0
Number of digital scroll high temperature alarms occurred to compressor 1 since the last
maintenance
S033
BONUS
0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS COMP2
Table 5-17 Descriptions of WELLNESS COMP2 parameters
Parameters
Default
Description
S035
STARTS
-
Number of compressor 2 starts since the last maintenance
S036
RUN HRS
hr
Compressor 2 run hours since the last maintenance
S037
AVG RUN
min
Average compressor 2 run time calculated through the number of starts and run hours