DVC6000 Digital Valve Controllers
September 2013
4-2
Detailed Setup (1-2)
Note
Detailed Setup is not available for
instrument level AC.
The Detailed Setup selection from the Configure menu
allows you to configure the digital valve controller to
your application. Table 4-1 lists the default settings for
a standard factory configuration. You can adjust
actuator response, set the various modes, alerts,
ranges, travel cutoffs and limits. You can also restart
the instrument and set the protection.
Mode and Protection (1-2-1)
Mode
Instrument Mode—You can change the
instrument mode by selecting Mode and Protection,
Instrument Mode from the Detailed Setup menu, or
press the Hot Key and select Instrument Mode.
Instrument Mode allows you to either take the
instrument Out Of Service or place it In Service.
Taking the instrument Out Of Service allows you to
perform instrument calibration and also allows you to
change setup variables that affect control, provided
the calibration/configuration protection is properly set.
See Setting Protection.
Note
Some changes that require the
instrument to be taken Out Of Service
will not take effect until the instrument
is placed back In Service or the
instrument is restarted.
Table 4-1. Factory Default Detailed Setup Parameters
Setup Parameter
Default Setting
(1)
Instrument
Configuration
Control Mode
Analog
Restart Control Mode
Resume Last
Zero Power Condition
Valve Open
(2)
Analog In Range Low
4 mA
Analog In Range High
20 mA
Analog Input Units
mA
Feedback Connection
Rotary
−
All
Travel Sensor Motion
Clockwise
Auxiliary Terminal Action
Disabled
Maximum Supply Pressure
20
Pressure Units
PSI
Temperature Units
F
Polling Address
0
Burst Mode Enable
No
Burst Command
3
Cmd 3 Configured Pressure
A
−
B
Dynamic
Response and
Tuning
Tuning Set
F
(2)
Input Characteristic
Linear
Travel Limit High
125%
Travel Limit Low
−
25%
Travel/Pressure Cutoff High
99.46%
Travel/Pressure Cutoff Low
0.50%
Set Point Rate Open
(3)
0%/sec
Set Point Rate Close
(4)
0%/sec
Set Point Filter Lag Time
0 sec
Integrator Enable
Yes
Integral Gain
9.4 repeats/minute
Integral Dead Zone
0.26%
Travel History
Alerts
Cycle Counter Alert Enable
No
Cycle Counter Alert Deadband
1%
Cycle Counter Alert Point
1000000
Travel Accumulator Alert
Enable
No
Travel Accumulator Deadband
1%
Travel Accumulator Alert Point
1000000
Deviation &
Other Alerts
Travel Deviation Alert Enable
Yes
Travel Deviation Alert Point
5%
Travel Deviation Time
9.99 sec
Pressure Deviation Alert
Enable
Yes
Pressure Deviation Alert Point
5 psi
Pressure Deviation Alert Time
9.99 sec
Drive Signal Alert Enable
Yes
Supply Pressure Alert Enable
Yes
Supply Pressure Alert Point
19 psi
Travel Alerts
Travel Alert Lo Enable
No
Lo Point
−
25%
Travel Alert Hi Enable
No
Hi Point
125%
Travel Alert Lo Lo Enable
No
Lo Lo Point
−
25%
Travel Alert Hi Hi Enable
No
Hi Hi Point
125%
Deadband
5%
Electronic
Alerts
Shutdown Activated
Yes
Low Power Write Fail Enable
No
Non-Critical NVM Alert Enable
No
−
continued on next page
−
4
Содержание Fisher FIELDVUE DVC6000
Страница 2: ......
Страница 22: ...DVC6000 Digital Valve Controllers September 2013 1 12 1 ...
Страница 82: ...DVC6000 Digital Valve Controllers September 2013 4 22 4 ...
Страница 94: ...DVC6000 Digital Valve Controllers September 2013 5 12 5 ...
Страница 139: ...Loop Schematics Nameplates September 2013 B 1 B B Appendix B Loop Schematics Nameplates B ...
Страница 161: ......