DVC6000 Digital Valve Controllers
September 2013
3-2
Instrument Mode
To setup and calibrate the instrument, the instrument
mode must be Out Of Service.
To view the instrument mode, press the Hot Key and
select Instrument Mode. If the mode is not Out Of
Service, select Out Of Service from the Instrument
Mode menu and press ENTER.
Configuration Protection
To setup and calibrate the instrument, the protection
must be set to None with the Field Communicator. If
the protection is not None, changing the protection
requires placing a jumper across the Auxiliary
terminals in the terminal box.
To remove protection:
1. Connect a 4-20 mA source to the instrument.
2. Connect the Field Communicator to the instrument
and turn it on.
3. Press the Hot key on the Field Communicator and
select Protection.
Note
If the Auxiliary Terminal Action is
configured for Auto Calibration, be
sure the jumper remains across the
auxiliary terminals until the Field
Communicator prompts you to remove
it. Removing the jumper too soon will
cause the instrument to begin auto
travel calibration.
4. From the Protection menu, select None. When
prompted by the Field Communicator, temporarily
attach the jumper to the AUX + and AUX
−
terminals
in the instrument terminal box.
Basic Setup (1-1)
WARNING
Changes to the instrument setup may
cause changes in the output pressure
or valve travel. Depending on the
application, these changes may upset
process control, which may result in
personal injury or property damage.
Note
To setup and calibrate the instrument,
the protection must be None and the
Instrument Mode must be Out Of
Service. See Configuration Protection
and Instrument Mode at the beginning
of this section for information on
removing instrument protection and
changing the instrument mode.
If you are operating in burst mode, we
recommend that you disable burst
before continuing with calibration.
Once calibration is complete, burst
mode may then be turned back on.
When the DVC6000 digital valve controller is ordered
as part of a control valve assembly, the factory
mounts the digital valve controller and sets up the
instrument as specified on the order. When mounting
to a valve in the field, the instrument needs to be
setup to match the instrument to the valve and
actuator.
Before beginning Basic Setup, be sure the instrument
is correctly mounted as described in the Installation
section.
Setup Wizard (1-1-1)
To have the Field Communicator automatically setup
the instrument using specified actuator information,
from the Online Menu select Configure, Guided Setup,
and Setup Wizard. Follow the prompts on the Field
Communicator display to setup the instrument. Table
4-5 provides the actuator information required to setup
and calibrate the instrument.
1. Select travel or pressure control. Travel control is
the typical mode of operation.
2. Enter the pressure units: psi, bar, kPa, or kg/cm
2
.
3
Содержание Fisher FIELDVUE DVC6000
Страница 2: ......
Страница 22: ...DVC6000 Digital Valve Controllers September 2013 1 12 1 ...
Страница 82: ...DVC6000 Digital Valve Controllers September 2013 4 22 4 ...
Страница 94: ...DVC6000 Digital Valve Controllers September 2013 5 12 5 ...
Страница 139: ...Loop Schematics Nameplates September 2013 B 1 B B Appendix B Loop Schematics Nameplates B ...
Страница 161: ......