Parameter
Name
Setting range
Min.
unit
Default Mod.
F8.01
Modbus data format
0: RTU, 1 start bit, 8 data bits, 2 stop bits,
no parity
1: RTU, 1 start bit, 8 data bits, 1 stop bit,
even parity
2: RTU, 1 start bit, 8 data bits, 1 stop bit,
odd parity
3: ASCII, 1 start bit, 7 data bits, 2 stop
bits, no parity
4: ASCII, 1 start bit, 7 data bits, 1 stop
bit, even parity
5: ASCII, 1 start bit, 7 data bits, 1 stop
bit, odd parity
1 0 ×
F8.02
Local number
0 (broadcast address), 1 ~ 127
1
5
×
F8.03
Modbus
communication
failure detection
time
0: disable the function
0.1 ~ 100.0s
0.1s 0 ×
F8.04
Modbus
communication
delay
0.01 ~ 1.000s
0.001s 0.01s
×
F8.05
CAN
communication
station enable
Bit0: station 1 enable
Bit1: station 2 enable
Bit2: station 3 enable
Bit3: station 4 enable
Corresponding station =1 means to enable
the station
Corresponding station=0 means to disable
the station
1 0 ×
F8.06
CAN baud rate
selection
0: 10000bps
1: 20000bps
2: 40000bps
3: 80000bps
4: 1250000bps
1 0 ×
F8.07
CAN
communication
failure detection
time
0: disable the function
0.1 ~ 100.0s
0.1s 0s ×
F8.08
CAN
communication
delay
0.01 ~ 1.000s
0.001s 0.01s
×
F8.09 ~
F8.10
Reserved
7.10
Monitoring
And
Recording
Parameters