68 Chapter 5 Parameters
EV1000 Series General Purpose Variable Speed Drive User Manual
EV1000
U
V
W
PE
M
R
S
T
3-phase
power supply
QF
PLC
COM
VRF
VCI
GND
.
.
.
.
.
REV
.
.
.
P24
FWD
1~3k
.
PE
K1
K2
.
X1
.
X2
K3
K4
Fig. 5-57 Wiring for Remote and Local Control
Note
:
If factory setting is 000, no bundling of operating
command and frequency setting method.
F9.01 Auxiliary freq.
setting method
Range: 0
~
13
【0】
F9.02 Auxiliary
reference factor
Range: 0.00
~
9.99
【
1.00
】
F9.03 Digital auxiliary
ref.
Range: 0.00
~
650.0Hz
【
0.00Hz
】
F9.04 Digital auxiliary
ref. control
Range: 000
~
111
【000】
The preset frequency is the final result of the
combination of main frequency and auxiliary
frequency. F9.01~F9.04 are for auxiliary
frequency. Fig.5-57 shows the course of
frequency combination.
auxiliary freq.
preset freq.
factor
F9.05, F9.06
∑
f1
f2
f3
f4
no auxiliary freq. (F9.01=0)
digital setting
(
F9.01=1~3
)
analog setting
(
F9.01=4~13
)
main freq.
common operation freq. (F0.00=0~5)
MS freq.
(
F3.23~F3.29
)
simple PLC freq.
(
F4.00~F4.14
)
close-loop freq. (F5.00~F5.26)
Fig. 5-58 Preset Freq. Calculation Method
▲▼
Serial
port
UPDN
CCI
PULSE
VCI
Analog
Digital
Aux. ref. freq.
Gain processing
F9.02
Pre-processing
Initial value and sign
of aux. ref.
F9.03 and F9.04
Setting F9.04
Setting of F1.00
Setting
of
F9.01
Pre-processing
Fig. 5-59 Auxiliary Frequency Processing
Table 5-12 Auxiliary Freq. Setting Method
Setting
Description
Note
0
No auxiliary freq.
Auxiliary freq.=0
1
Digital setting 1,
adjust by
▲
and
▼
2
Digital setting 2,
adjust by UP/DN
3
Digital setting 3, set
by serial port
Set by F9.03. Whether
the frequency before
power failure will be
saved depending the
setting of F9.04.
4
VCI analog setting
5
CCI analog setting
6 Terminal
PULSE
7
- VCI analog setting
8
- CCI analog setting
9 -Terminal
PULSE
10 VCI-5
11 CCI-5
12 PULSE-0.5×F1.03
13 Potentiometer
Depend on actual input.
Refer to F1.00.
Select digital setting 3, you may set F9.03 via