106 Appendix 1 Parameter Set
EV1000 Series General Purpose Variable Speed Drive User Manual
F5: Close-loop Control
Para.
Name
Range
Unit Default Modification
F5.00 Close loop control
0: disabled
1: enabled
1
0
×
F5.01 Reference input method
0: digital setting
Take the value of F5.05 if F5.02
=
1~5;
Take the value of F5.06, if F5.02
=
6.
1: VCI (0
~
10V)
2: CCI
Pay attention to the setting of jumper CN10.
3: Keypad
4: PULSE
Note: for speed close loop control, the analog input
10V or max. input pulse freq. F1.03 corresponds to
the synch speed of F0.05.
1
1
○
F5.02 Feedback method
0: VCI analog voltage 0
~
10V
1: CCI analog input
2: VCI + CCI
3: VCI-CCI
4: Min {VCI,CCI}
5: Max {VCI, CCI}
6: pulse (PG close-loop single-phase or 2-phase
feedback decided by terminal)
1
1
○
F5.03 Input filter
0.01
~
50.00s
0.01s
0.50s
○
F5.04 Feedback filter
0.01
~
50.00s
0.01s
0.50s
○
F5.05 Digital reference input
0.00V
~
10.00V
0.01
0.00
○
F5.06 Speed close loop
setting
0
~
39000rpm
1
0
○