Section 4 - Lightning & Surge
Page 4-1
S1400T-2808B
Section 4 - Lightning Arresters & Surge Protectors
4.1 STROKES & STRIKES
Lightning takes the form of a pulse that typically has a 2 µS rise and a 10 µS to 40 µS decay
to a 50% level. The IEEE standard is an 8 µS by 20 µS waveform. The peak current will
average 18 KA for the first impulse and about half of that for the second and third
impulses. Three strokes (impulses) is the average per lightning strike. The number of
visible flashes that may be seen is not necessarily the number of electrical strokes.
A lightning strike acts like a constant current source. Once ionization occurs, the air
becomes a luminous conductive plasma reaching up to 60,000° F. The resistance of a struck
object is of little consequence except for the power dissipation on the object (I
2
x R). Fifty
percent of all lightning strikes will have a first impulse of at least 18 KA, ten percent will
exceed the 60 KA level, and only about one percent will exceed 120 KA.
4.1.1 Chance of Being Struck by Lightning
The map of Figure 4-1 shows the average annual number of thunderstorm days
(Isokeraunic level) for the various regions within the continental U.S.A. This map is not
representative of the severity of the storm or the number of lightning strikes since it does
not take into account more than one lightning strike in a thunderstorm day. The
Isokeraunic or Isoceraunic number provides a meteorological indication of the frequency of
thunderstorm activity; the higher the Isokeraunic number the greater the lightning strike
activity for a given area. These levels vary across the world from a low of 1 to a high of 300.
Within the United States the Isokeraunic level varies from a low of 1 to a high of 100.
Figure 4-1 - Average Thunderstorm Days of the Year (for Continental USA)
Содержание Bristol 2808 Series
Страница 12: ...BLANK PAGE ...
Страница 14: ...1 2 Introduction 2808B Figure 1 1 2808 XXB Transmitters ...
Страница 16: ...BLANK PAGE ...
Страница 23: ...2808B GP Transmitters 1A 7 Figure 1A 5 Overall Dimensions Model 2808 15B With Neck Type Mounting Bracket ...
Страница 24: ...1A 8 GP Transmitters 2808B Figure 1A 6 Overall Dimensions Model 2808 16B With Neck Type Mounting Bracket ...
Страница 30: ...BLANK PAGE ...
Страница 32: ...1B 2 DP Transmitters 2808B Figure 1B 1 Model 2808 35B Figure 1B 2 Transmitter Assemblies ...
Страница 37: ...2808B DP Transmitters 1B 7 Figure 1B 4C Dimensions for Model 2808 35B Transmitter With Manifold Adapter Option ...
Страница 40: ...1B 10 DP Transmitters 2808B Figure 1B 6 Transmitter Housing Rotation Diagram ...
Страница 54: ...BLANK PAGE ...
Страница 57: ...2808B Calibration 3 3 Figure 3 2 Calibration Adjustments ...
Страница 60: ...3 6 Calibration 2808B TABLE 3 A COARSE ZERO SWITCH SETTINGS Elevation ...
Страница 61: ...2808B Calibration 3 7 TABLE 3 B COARSE ZERO SWITCH SETTINGS Suppression ...
Страница 66: ...BLANK PAGE ...
Страница 68: ...4 2 Service 2808B Figure 4 1 Using Internal TEST Terminals to Measure Current ...
Страница 72: ...BLANK PAGE ...
Страница 74: ...BLANK PAGE ...
Страница 81: ...Appendix B Page 5 Loop Powered Indicator Figure 2 2 Loop Powered Indicator Installation Diagram ...
Страница 90: ...BLANK PAGE ...
Страница 92: ...BLANK PAGE ...
Страница 100: ...BLANK PAGE ...
Страница 127: ...ESDS Manual S14006 4 15 92 CARE AND HANDLING OF PC BOARDS AND ESD SENSITIVE COMPONENTS BRISTOL BABCOCK ...
Страница 128: ...BLANK PAGE ...
Страница 139: ...BLANK PAGE ...