1B-14 / DP Transmitters
2808B
Figure 1B-15 - Closed Tank with Air Purge
The purge meter (pressure regulator) maintains a pressure on the dip tube that is
about 5% above the maximum pressure of a full tank. This prevents the liquid from
backing up the dip tube into the HI side of the Transmitter. For this application, the
liquid in the tank should not be allowed to exceed the maximum (100%) measurement
level or else it may backflow into the LO side of the Transmitter.
Head Error.
A head error results whenever the transmitter is positioned above or
below the minimum (0%) measurement level of the tank. Head errors will add to or
sub-tract from the tank zero readings. These errors can be corrected during range
calibration to obtain the proper output readings. See Section 3 for calibration
information.
1B.6 SERVICE CHECKS
General troubleshooting hints are listed in Table 1B-B. Some of these checks will require a
digital multimeter (DMM). The DMM may be connected across the (+) and (V) terminals to
measure current directly without opening the current loop. See
Section 4 - Service
for
details.
Содержание Bristol 2808 Series
Страница 12: ...BLANK PAGE ...
Страница 14: ...1 2 Introduction 2808B Figure 1 1 2808 XXB Transmitters ...
Страница 16: ...BLANK PAGE ...
Страница 23: ...2808B GP Transmitters 1A 7 Figure 1A 5 Overall Dimensions Model 2808 15B With Neck Type Mounting Bracket ...
Страница 24: ...1A 8 GP Transmitters 2808B Figure 1A 6 Overall Dimensions Model 2808 16B With Neck Type Mounting Bracket ...
Страница 30: ...BLANK PAGE ...
Страница 32: ...1B 2 DP Transmitters 2808B Figure 1B 1 Model 2808 35B Figure 1B 2 Transmitter Assemblies ...
Страница 37: ...2808B DP Transmitters 1B 7 Figure 1B 4C Dimensions for Model 2808 35B Transmitter With Manifold Adapter Option ...
Страница 40: ...1B 10 DP Transmitters 2808B Figure 1B 6 Transmitter Housing Rotation Diagram ...
Страница 54: ...BLANK PAGE ...
Страница 57: ...2808B Calibration 3 3 Figure 3 2 Calibration Adjustments ...
Страница 60: ...3 6 Calibration 2808B TABLE 3 A COARSE ZERO SWITCH SETTINGS Elevation ...
Страница 61: ...2808B Calibration 3 7 TABLE 3 B COARSE ZERO SWITCH SETTINGS Suppression ...
Страница 66: ...BLANK PAGE ...
Страница 68: ...4 2 Service 2808B Figure 4 1 Using Internal TEST Terminals to Measure Current ...
Страница 72: ...BLANK PAGE ...
Страница 74: ...BLANK PAGE ...
Страница 81: ...Appendix B Page 5 Loop Powered Indicator Figure 2 2 Loop Powered Indicator Installation Diagram ...
Страница 90: ...BLANK PAGE ...
Страница 92: ...BLANK PAGE ...
Страница 100: ...BLANK PAGE ...
Страница 127: ...ESDS Manual S14006 4 15 92 CARE AND HANDLING OF PC BOARDS AND ESD SENSITIVE COMPONENTS BRISTOL BABCOCK ...
Страница 128: ...BLANK PAGE ...
Страница 139: ...BLANK PAGE ...