Appendix B
Page 9
Loop Powered Indicator
If the selected unit is mA or % no further configuration is allowed and configuration
mode ends. For other units the following occurs.
The SET LO legend appears with the minus sign blinking, and the previously con-
figured digits for the Zero appear without a decimal point. Previously configured minus
sign and ten-thousandths half-digit choices are cancelled, and new selections must be
made. Press Select to make the minus active, press Mode to skip over it. The ten-
thousandths digit (a one) begins blinking after the minus sign has been configured.
Again, press Select to make it active, press Mode to skip over it.
After the ten-thousandths digit is selected the thousands (leftmost) full digit will begin
blinking.
3. Press the Select button to increment the digit (zero to nine) or press Mode to leave the
digit as it is and activate the next digit location to the right. Repeat until all digits
have been set.
When Mode is pressed while the units (rightmost) digit location is blinking decimal
point locations 2 and 5 will start blinking. As with units, a selection MUST be made or
the Mode button will just cycle through all decimal point choices. When decimal point
locations 2 and 5 are blinking simultaneously this indicates a “no decimal” choice,
meaning that the decimal point is “hidden” on the far right of the display.
4. Press the Mode button to display the next decimal point choice, which will be the
location to the left of the rightmost digit. As the Mode button is pressed the blinking
decimal point will shift to the left in the display and eventually wrap-around to repeat
the simultaneous display of locations 2 and 5. Press the Select button to make the
blinking decimal point location active and move to the configuration of Full-scale.
When the Zero decimal point is selected the SET LO legend will disappear and the SET
HI legend will appear. The minus sign location will be blinking, and the digit locations
will contain previously configured Full-scale values.
5. Use the Mode and Select buttons to configure the minus sign, ten-thousandths digit,
thousandths to units, and decimal point. When the decimal point is selected
configuration is complete. The SET HI legend will disappear, blinking will stop and the
unit will exit Configuration mode and enter Run mode.
6. Upon exit from configuration mode the selected configuration (Base Unit, BU) is stored
in an EEPROM where it remains until another configuration occurs. Current is always
converted to and displayed in the selected BU henceforth.
If the selected unit is mA or % only the unit selection itself is stored.
If the selected unit is one of the four pressure units (psi, inH2O, bar, kg/cm2) then the
zero and full scale of the other pressure units are converted to be proportional to the
BU and then stored. This means that the zero and full scale of a selected BU of psi are
converted to the other pressure units and saved along with the BU zero and full scale.
If the selected BU is one of the two temperature units (Celsius, Fahrenheit) then the
other temperature unit zero and full scale are converted and then saved.
Содержание Bristol 2808 Series
Страница 12: ...BLANK PAGE ...
Страница 14: ...1 2 Introduction 2808B Figure 1 1 2808 XXB Transmitters ...
Страница 16: ...BLANK PAGE ...
Страница 23: ...2808B GP Transmitters 1A 7 Figure 1A 5 Overall Dimensions Model 2808 15B With Neck Type Mounting Bracket ...
Страница 24: ...1A 8 GP Transmitters 2808B Figure 1A 6 Overall Dimensions Model 2808 16B With Neck Type Mounting Bracket ...
Страница 30: ...BLANK PAGE ...
Страница 32: ...1B 2 DP Transmitters 2808B Figure 1B 1 Model 2808 35B Figure 1B 2 Transmitter Assemblies ...
Страница 37: ...2808B DP Transmitters 1B 7 Figure 1B 4C Dimensions for Model 2808 35B Transmitter With Manifold Adapter Option ...
Страница 40: ...1B 10 DP Transmitters 2808B Figure 1B 6 Transmitter Housing Rotation Diagram ...
Страница 54: ...BLANK PAGE ...
Страница 57: ...2808B Calibration 3 3 Figure 3 2 Calibration Adjustments ...
Страница 60: ...3 6 Calibration 2808B TABLE 3 A COARSE ZERO SWITCH SETTINGS Elevation ...
Страница 61: ...2808B Calibration 3 7 TABLE 3 B COARSE ZERO SWITCH SETTINGS Suppression ...
Страница 66: ...BLANK PAGE ...
Страница 68: ...4 2 Service 2808B Figure 4 1 Using Internal TEST Terminals to Measure Current ...
Страница 72: ...BLANK PAGE ...
Страница 74: ...BLANK PAGE ...
Страница 81: ...Appendix B Page 5 Loop Powered Indicator Figure 2 2 Loop Powered Indicator Installation Diagram ...
Страница 90: ...BLANK PAGE ...
Страница 92: ...BLANK PAGE ...
Страница 100: ...BLANK PAGE ...
Страница 127: ...ESDS Manual S14006 4 15 92 CARE AND HANDLING OF PC BOARDS AND ESD SENSITIVE COMPONENTS BRISTOL BABCOCK ...
Страница 128: ...BLANK PAGE ...
Страница 139: ...BLANK PAGE ...