Eltako – The System in the Building – Operating manual for Series 14 RS485 bus DIN rail mounted devices
15
Remote switch system FTS14
ID range:
The lower rotary switch defines the group to which an FTS14EM belongs. A total of 5 groups are available (1, 101, 201, 301 and 401)
each with 100 IDs. The decade ID within a group, which can contain max 10 FTS14EM devices, is set using the upper rotary switch (0-
90). The ID range then results from the combination of upper and lower rotary switches and must be set differently on each FTS14EM.
Every FTS14EM can be set either to UT (= universal pushbutton) or to RT (= direction pushbutton) using the lower rotary switch. The LED
under the upper rotary switch flickers briefly when a connected pushbutton is pressed.
Function test:
The LED under the upper rotary switch flashes briefly when a connected sensor is operated and lights up permanently when a con-
nection to FAM14 or FTS14KS was set up by PCT14.
Notes on PCT14:
The FTS14EM receives no device address and is therefore not displayed as a device in the PCT14 software. However, the ID tele-
grams generated by the input module can be displayed by means of the ID identifier. Alternatively, predefined ID lists are available.
This allows the input modules FTS14EM to quickly assign an ID to an actuator.