BCU 480 · Edition 06.07
45
Behaviour of the air valve in the event of a fault lock-out
5 .7 .9
Parameter 32
This determines whether the air valve can be activated in
the case of a fault lock-out.
Parameter 32 = 0: The air valve is closed in the event of a
fault. It cannot be activated externally via terminal 23.
Parameter 32 = 1: The air valve can be activated externally
via input 23 even during a fault, e.g. for cooling.
Parameters > Air valve control on BCU . .L