UVS check
5 .2 .6
Parameter 35
An automatic restart of the burner control unit can be activated
every 24 hours via this parameter. The time starts each time
the start-up signal (
ϑ
) is applied.
Parameter 35 = 0 Unlimited burner operation.
Parameter 35 = 1: An automatic restart is activated once every
24 hours.
It must be ensured in this case that the program sequence
started matches the application. This parameter may be set
in this way only if the burner can restart as intended in all
operating phases.
Parameters > Flame control