BCU 480 · Edition 06.07
61
Flame control:
sensor voltage approx. 230 V AC,
sensor current > 1 μA.
Length of sensor cable: max. 50 m (164 ft).
Fuse in unit:
F1: 3.15 A, slow-acting, H pursuant to IEC 127-2/5,
F3: 3.15 A, slow-acting, H pursuant to IEC 127-2/5.
Ambient temperature: -20 to +60°C (-4 to +140°F),
Climate: no condensation permitted.
Enclosure: IP 54 pursuant to IEC 529.
Max. number of operating cycles: 1,000,000,
Mains switch: 1,000,
Reset/Information button: 1,000.
Input/Output safety circuit:
All inputs/outputs marked with “ ” (see connection dia-
gram) may be used for safety tasks.
Weight: approx. 5 kg (11 lb) depending on version.
BCU . .B1
External fuse: 12 A per zone.
Technical data