BCU 480 · Edition 06.07
53
Installation
7 .8
Recommended installation position: vertical (cable glands
pointing downwards).
When installing, ensure that there is sufficient space to open
the BCU.
From inside
Open BCU and screw on with four screws (Ø 4 mm, min. length
15 mm).
From outside
163 mm
185 mm
7 .28"
6 .42"
Screw on the closed unit to the rear with 4 self-tapping screws
(enclosed).
Otherwise, mount with external securing bars or fastening
set (see Accessories).
Wiring
7 .9
Electrical connection via plug-in connection terminals (2.5
mm
2
) and plug-in cable glands. The latter can be removed
in order to facilitate installation. The BCU is suitable for hard
wiring only. Do not reverse phase and neutral conductor. Dif-
ferent phases of a three-phase current system must not be
installed at the BCU. No voltage may be connected to the
valve and ignition outputs.
Project planning information