65
Parameter setting
Sensor Sewi KNX TH-L-Pr
• Version: 17.11.2016 • Technical changes and errors excepted.
6.17. Comfort field
The
Sensor Sewi KNX TH-L-Pr
can send a message to the bus if the limits of the
comfort field are exceeded. In this way, it is for example possible to monitor complian-
ce with DIN 1946 (standard values) or even to define your own comfort field.
Specify the
sending pattern
, a
Text
for comfortable and uncomfortable and the
Ob-
ject value
.
Define the comfort field by specifying the minimum and maximum values for tempe-
rature and humidity. The specified standard values comply with DIN 1946
Temperature hysteresis: 1°C
Use absolute humidity
No • Yes
Sending pattern
• never
• periodically
• on change
• on change and periodically
At and above change of
(if sent on change)
0.1 g • 0.2 g • 0.5 g • 1.0 g • 2.0 g • 5.0 g
Send cycle
(if sent periodically)
5 s • 10 s • 30 s… • 2 h
Use comfort field
No • Yes
Sending pattern
• never
• periodically
• on change
• on change and periodically
Text for comfortable
[Free text max. 14 chars.]
Text for uncomfortable
[Free text max. 14 chars.]
Object value is at
• comfortable = 1 | uncomfortable = 0
• comfortable = 0 | uncomfortable = 1
Send cycle
(if sent periodically)
5 s • 10 s • 30 s… • 2 h
Maximum temperature in °C
(Standard 26°C)
25 ... 40; 26
Minimum temperature in °C
(Standard 20°C)
10 ... 21; 20
Maximum relative humidity in %
(
Standard 65%)
52 ... 90; 65
Minimum relative humidity in %
(Standard 30%)
10 ... 43; 30
Maximum absolute humidity in 0.1 g/kg
(Standard 115 g/kg)
50 ... 200; 115