39
Parameter setting
Sensor Sewi KNX TH-L-Pr
• Version: 17.11.2016 • Technical changes and errors excepted.
The
minimum and maximum readings
can be saved and sent to the bus. Use the
"Reset temperature min/max. value" objects to reset the values to the current readings.
The values are not retained after a reset.
6.6.
Temperature threshold values
Activate the required temperature threshold values. The menus for setting the th-
reshold values are displayed.
6.6.1. Threshold value 1, 2, 3, 4
Threshold value
Set, in which cases
threshold values and delay times
received via object are to be
retained. The parameter is only taken into consideration if the setting via object is ac-
tivated below. Please note that the setting "After power supply restoration and pro-
gramming" should not be used for the initial start-up, as the factory settings are always
used until the first communication (setting via objects is ignored).
Set the threshold value directly in the application program using parameters, or define
them via the bus using a communication object.
Threshold value setting via parameter:
Set the threshold values and hysteresis directly.
Ext. Reading proportion of the total reading
5% • 10% • ... • 50% • ... • 100%
Sending pattern for internal and total mea-
sured value
• never
• periodically
• on change
• on change and periodically
At and above change of
(if sent on change)
0.1°C • 0.2°C • 0.5°C • ... • 5.0°C
Send cycle
(if sent periodically)
5 s • 10 s • ... • 2 h
Use minimum and maximum value
No • Yes
Use threshold value 1/2/3/4
Yes • No
Maintain the
threshold values and delays received via
communication objects
• never
• after power supply restoration
• after power supply restoration and
programming
Threshold value setting via
Parameter
• Communication objects
Threshold value in 0.1°C
-300 … 800; 200